8. CAPACITY TABLES
<Heating>
(1) Nominal power input of outdoor unit
(2) Calculation of the average indoor temperature power input coefficient
Average indoor temp. power input coefficient (
= 0.8 × 36/(36 + 36 + 0.8 × 36/(36 + 36
= 0.80
(3) Coefficient of the partial load (CTi/CTo)
(4) Outdoor power input (PIo)
Maximum System Capacity (CTx = Total Indoor unit Capacity (CTi , so use the following formula
PIo = Outdoor unit Heating Nominal Power Input × Correction Coefficient of Indoor temperature × ƒ
= 5.48 × 0.8 × 0.94
= 4.12 kW
MEES21K108
n
c
=
{c
×
(M
k
ave
k=1
n: Total number of the indoor units
k: Number of the indoor unit
c
: Outdoor unit power input coefficient of k indoor unit room temp.
k
M
: Number part of the k indoor unit model (e.g. P36
k
5.48 kW (Nominal)
0.80
0.80
n
/
M
k
k
k=1
0.94
Hyper Heating Inverter Y-Series
35