11. M-NET CONTROL
11-4-2. Rule of setting address
Unit
Address setting
Indoor unit
System control interface
(MAC-333IF-E)
01 ~ 50
A-M converter
(PAC-IF01MNT-E)
51 ~ 99, 100
Outdoor unit
(Note1)
BC controller
52 ~ 99, 100
(Main)
BC controller
52 ~ 99, 100
(Sub)
ME, Lossnay
Remote controller
101 ~ 150
(Main)
ME, Lossnay
Remote controller
151 ~ 199, 200
(Sub)
ON/OFF remote
201 ~ 250
controller
AE-200A/AE-50A
AG-150A-A
EB-50GU-A
000, 201 ~ 250
EW-50A
TC-24B
000, 201 ~ 250
PAC-YG50ECA
000, 201 ~ 250
BAC-HD150
LMAP04U-E
201 ~ 250
PAC-YG60MCA
01 ~ 50
PAC-YG63MCA
01 ~ 50
PAC-YG66DCA
01 ~ 50
01 ~ 50
Lossnay
PAC-IF01AHC-J
201 ~ 250
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
MEES21K108
Example
Use the most recent address within the same group of indoor units. Make the
indoor units address connected to the BC controller (Sub) larger than the indoor
units address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
10
1
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
The smallest address of indoor unit in same refrigerant system + 50
Assign sequential address numbers to the outdoor units in one refrigerant circuit
system. OC and OS are automatically detected. (Note 2)
Please reset one of them to an address between 51 and 99 when two addresses
10
1
overlap.
The address automatically becomes "100" if it is set as "01~ 50"
The address of outdoor unit + 1
Please reset one of them to an address between 51 and 99 when two addresses
overlap.
10
1
The address automatically becomes "100" if it is set as "01~ 50"
Lowest address within the indoor units connected to the BC controller (Sub) plus 50.
10
1
The smallest address of indoor unit in the group + 100
1
The place of "100" is fixed to "1"
Fixed
10
1
The address of main remote controller + 50
1
The address automatically becomes "200" if it is set as "00"
Fixed
10
1
The smallest group No. to be managed + 200
The smallest group No. to be managed is changeable.
100
10
1
0, 2
0-5
0-9
TC-24B cannot be set to "000".
100
10
1
0, 2
0-5
0-9
Settings are made on the initial screen of AG-150A-A.
100
10
1
0, 2
0-5
0-9
Settings are made with setting tool of BM ADAPTER.
100
10
1
2
Fixed
10
1
10
1
10
1
10
1
After setting the addresses of all the indoor units, assign an arbitrary address.
10
1
2
Fixed
10
1
Hyper Heating Inverter Y-Series
Note
86