Forta Proportional Control Auxiliary Switch (Optional) Setup Reference
Switch 1
Switch 2
% of Valve Travel
With the actuator powered and being controlled by the input signal the optional auxiliary switches only transfer contacts as follows,
driving from full retract to full extend the auxiliary contacts transfer when the actuator is about 95% of full extend travel. When the
actuator drives from full extend to full retract the contacts will transfer when the actuator is about 95% of full retract travel.
Table 3
Auxiliary Switches
Program Switch 1off
2 - SPDT
Closed
KC1 - K1
KC1 - K2
X
KC2 - K3
X
KC2 - K4
Proportional Control
Action
Program Switches 1 off, 7 off
Low Signal Input
High Signal Input
Note: With power to the actuator off, Auxiliary Switches are made KC1 to K1 and KC2 to K3. Upon power up switches will
make as shown above after auto start up calibration.
Note: This table shows the auxiliary switch action based on the dip switch 1 and 7 settings. You should program the dip switches on the actuator
based on the application requirements, once programmed review this chart to determine the action of the auxiliary switches and wire the switches
accordingly. IF YOU CHANGE EITHER DIP SWITCH 1 or 7 TO GET A DIFFERENT CONTACT CLOSURE YOU WILL CHANGE THE
EXTEND/RETEACT MOVEMENT OF THE ACTUATOR.
VB-72XX Two Way Globe Valve, Forta Floating Control Setup Reference
Table 4
VB-72xx 2 way valves
Valve Type
Valve
position with
D2 powered
VB-722x stem
up closed
VB-722x stem
down open
VB-722x stem
up closed
VB-722x stem
down open
VB-721x stem
up open
VB-721x stem
down closed
VB-721x stem
up open
VB-721x stem
down closed
Programming Note: The above switch positions are the base programming configurations, in the base
configurations all other switches should be switched off. Once the base programming configuration has
been set up you may wish to add additional program features and functions that are listed below.
DIM119E
F-27506-1
CLOSE
OPEN
CLOSE
OPEN
0
10
20
30
Optional Auxiliary Switch Function (S2)
Example A
Example B
Program Switch 1on
Power Up
Power Up
Retracted
Extended
Open
Closed
X
X
X
X
Program Switches 1 on, 7 on
Retracts
Retracts
Extends
Extends
Forta M400A / M800A Base Floating Configuration
Program Switch Position
Power up
Switch 1 Switch 2 Switch 7
OFF
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
DA = Full open, full flow, 10vdc output / Full closed, no flow, 2vdc output
RA = Full open, full flow, 2vdc output / Full closed, no flow 10vdc output
40
50
60
70
80
Example C
Proportional Control
Program Switch 1off
Power Up
Retracted
Open
Closed
Open
X
X
X
X
X
X
Program Switches 1 off, 7 on
Extends
Retracts
Input / Output
Power to
Power to
D2 input
Feedback
D1 input
Position
terminal
signal
terminal
Retract
Retract
Extend
No Flow
No Flow
2 vdc
Full Flow
Retract
Extend
Retract
No Flow
Full Flow
10 vdc
No Flow
Extend
Retract
Extend
Full Flow
No Flow
10 vdc
Full Flow
Extend
Extend
Retract
Full Flow
Full Flow
2 vdc
No Flow
Extend
Retract
Extend
No Flow
Full Flow
10 vdc
No Flow
Extend
Extend
Retract
No Flow
No Flow
2 vdc
Full Flow
Retract
Retract
Extend
Full Flow
Full Flow
2 vdc
No Flow
Retract
Extend
Retract
Full Flow
No Flow
10 vdc
Full Flow
8 (10)
90
100
Example D
Program Switch 1on
Power Up
Extended
Closed
Open
X
X
X
X
Program Switches 1 on, 7 off
Extends
Retracts
Feedback
signal
10 vdc
2 vdc
2 vdc
10 vdc
2 vdc
10 vdc
10 vdc
2 vdc