ABB ACS880 Firmware Manual page 373

Winch control program (option +n5100)
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
KTY84 analog I/O
KTY84 encoder
module 1
KTY84 encoder
module 2
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
PTC DI6
Description
KTY84 sensor connected to the analog input selected by
parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control
unit or on an extension module.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the unit selection parameter of the input to volt.
• Set the source selection parameter of the analog
output to
"Force KTY84
• Select the analog input in parameter 35.24. In case the
input is located on an I/O extension module, use the
selection
Other
to point at the actual input value
parameter
(for example,
14.26 AI1 actual
The analog output feeds a constant current through the
sensor. As the resistance of the sensor changes along
with its temperature, the voltage over the sensor
changes. The voltage is read by the analog input and
converted into degrees.
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter
Pt100 sensor connected to a standard analog input
selected by parameter
35.24 Temperature 2 AI source
and an analog output. The input and output can be on the
drive control unit or on an extension module.
The required settings are the same as with selection
KTY84 analog
I/O, except that the source selection
parameter of the analog output must be set to
PT100
excitation.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
PTC sensor connected to digital input DI6 (see the
connection diagram on page 171).
Note: Either 0 ohm (normal temperature) or 4000 ohm
(excessive temperature) will be shown by
Measured temperature
2. By default, an excessive
temperature will generate a warning as per parameter
35.23 Temperature 2 warning
instead, set
35.22 Temperature 2 fault limit
and an analog
excitation".
value).
time.
time.
Force
I/O, but with two sensors
I/O, but with three sensors
35.03
limit. If you want a fault
to 4000 ohm.
Parameters 373
Def/FbEq16
2
3
4
5
6
7
8