Quick Start Guide
6.6.2
IA ATEX FISCO Intrinsic Safety
Certificate Baseefa09ATEX0093X
Standards EN IEC 60079-0:2018, EN 60079-11:2012
Markings
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards and light alloy or
zirconium enclosures must be protected from impact and friction
when installed.
2. The equipment is not capable of withstanding the 500 V insulation
test required by EN 60079-11:2011, clause 6.3.13. This must be
taken into account when installing the equipment.
6.6.3
N1 ATEX Zone 2 (with enclosure)
Certificate Baseefa09ATEX0095X
Standards EN IEC 60079-0:2018, EN 60079-7:2015 + A1:2018, EN
Markings
Special Conditions for Safe Use (X):
1. The equipment must only be installed in an area of pollution degree
2 or better, as defined in IEC 60664-1.
2. Provision must be made, external to the equipment, to ensure the
rated voltage of the equipment supply is not exceeded by transient
disturbances of more than 40 percent.
28
II 1 G Ex ia IIC T4 Ga (–50 °C ≤ T
per drawing 00848-4406
FISCO (input)
U
= 17.5 V
i
I
= 380 mA
i
P
= 5.32 W
i
C
= 2.1 nF
i
L
= 0
i
60079-15:2010
II 3G Ex nA IIC T5 Gc (-40 °C ≤ T
(-40 °C ≤ T
≤ +65 °C)
a
≤ +60 °C) when installed
a
Sensor field terminal (output)
U
= 12.5 V
O
I
= 4.8 mA
O
P
= 15 mW
O
C
= 1.2 μF
O
L
= 1 H
O
≤ +65 °C), Ex ec IIC T5 Gc
a
December 2021
Rosemount 848T