A. Integrated power conditioner and filter
B. 6234 ft. (1900 m) max (depending upon cable characteristics)
C. Terminators (trunk)
D. Power supply
E. F
F. Spurs
G. Signal wiring
H. Devices 1-16 (intrinsically safe installations may allow fewer devices per
I.S. barrier)
3.4.1
Ground the transmitter
Proper ground is crucial to reliable temperature readings.
3.4.2
Ungrounded thermocouple, mV, and RTD/Ohm inputs
Option 1
Procedure
1. Connect F
shield(s).
2. Ensure the shields are tied together and electrically isolated from the
transmitter enclosure.
3. Only ground the shield at the power supply end.
4. Ensure that the sensor shield(s) is electrically isolated from the
surrounding grounded fixtures.