Chauvin Arnoux AEMC AmpFlex User Manual

Chauvin Arnoux AEMC AmpFlex User Manual

Flexible ac currrent probe

Advertisement

Quick Links

AmpFlex
®
CURRENT PROBES
Flexible
AC Current
Probe
E N G L I S H
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for Chauvin Arnoux AEMC AmpFlex

  • Page 1 AmpFlex ® CURRENT PROBES Flexible AC Current Probe E N G L I S H User Manual...
  • Page 2 , Inc. has made every reasonable effort to ensure that this documentation is accurate; ® but does not warrant the accuracy or completeness of the text, graphics, or other information contained in this documentation. Chauvin Arnoux , Inc. shall not be liable for any damages, special, indirect, ®...
  • Page 3 Statement of Compliance Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ® ® certifies that this instrument has been calibrated using standards and instruments traceable to international standards. We guarantee that at the time of shipping your instrument has met its published specifications.
  • Page 4: Table Of Contents

    TABLE OF CONTENTS 1. INTRODUCTION ................5 1.1 PRECAUTIONS FOR USE ..........6 1.2 RECEIVING YOUR SHIPMENT ..........6 1.3 PACKAGING ................6 2. PRODUCT FEATURES ..............7 2.1 DESCRIPTION ................7 2.2 AMPFLEX ................. 8 ® 2.3 FEATURES ................. 9 2.4 ACCESSORIES ................
  • Page 5: Introduction

    1. INTRODUCTION Thank you for purchasing an AEMC Instruments AmpFlex Flexible AC ® ® Current Probe. For best results from your instrument and for your safety, read the enclosed operating instructions carefully and comply with the precautions for use. These products must only be used by qualified and trained users.
  • Page 6: Precautions For Use

    1.1 PRECAUTIONS FOR USE These safety warnings are provided to ensure the safety of personnel and proper operation of the instrument. ■ Read the instruction manual completely and follow all the safety information before attempting to use or service this instrument. ■...
  • Page 7: Product Features

    2. PRODUCT FEATURES 2.1 DESCRIPTION The AmpFlex is a flexible AC current transformer composed of a flexible ® sensor and an electronic module. The flexible sensor permits measurements on conductors where standard clamp-on probes could not be used. In particular, it can be installed in tight spaces, around breaker panels, around cable bundles, around wide or large bus bars, or even wrapped around irregular shapes.
  • Page 8: Ampflex

    2.2 AMPFLEX ® Figure 1 Positive: Red Banana Plug (+). Common: Black Banana Plug (-). Power ON Indicator (Green LED). Overload Indicator (Red LED). Range Selection Switch. AmpFlex Connector/Latch. ® Flexible Sensor (Diameter 0.5”, 12.5mm). Lead from Sensor to Module (6.5ft, 2m). Electronic Module - Descriptive Label on Back Case (range, model, etc.) AmpFlex...
  • Page 9: Features

    2.3 FEATURES ■ Models to measure from 0.5 Arms to 30,000 Arms. ■ Accuracy: 1% of reading. ■ TRMS measurements when connected to a TRMS instrument. ■ No core saturation or damage if overloaded. ■ Overrange LED for measurement circuitry. ■...
  • Page 10: Standard Models

    2.5 STANDARD MODELS Measurement Sensor Model Output Conductor Cat. # Range Length Size 24” 8” 300-24-2-10 30/300A 100/10mV/A 2112.88 (610mm) (190mm) 24” 8” 1000-24-1-1 1000A 1mV/A 2112.39 (610mm) (190mm) 36” 11” 1000-36-2-1 100/1000A 10/1mV/A 2113.00 (910mm) (290mm) 24” 8” 3000-24-1-1 3000A 1mV/A 2112.46...
  • Page 11: Operation

    3. OPERATION Please ensure that you have already read and fully understand the Precautions for Use section on page 6. 3.1 MAKING MEASUREMENTS WITH THE AMPFLEX ® ■ Connect the electronic module to the AC Volt range of your Digital Multi-Meter (DMM) or measuring instrument.
  • Page 12 TIPS FOR MAKING PRECISE MEASUREMENTS (CONTINUED) ■ To increase sensitivity or measure on low currents, the AmpFlex may be ® wrapped several times around the conductor. Divide your reading by the number of turns for the actual measurement (see Figure 4). ■...
  • Page 13 TIPS FOR MAKING PRECISE MEASUREMENTS (CONTINUED) ■ The AmpFlex may be doubled around the conductor to be measured to ® double the output (see Figures 3 and 4 to show the different values on a DMM while measuring 250Aac). One turn around a conductor carrying 250Aac. Figure 3 AmpFlex Current Probe...
  • Page 14 TIPS FOR MAKING PRECISE MEASUREMENTS (CONTINUED) Double the turns to double the output in low-current applications or for higher sensitivity. Figure 4 AmpFlex Current Probe ®...
  • Page 15: Typical Response Curves

    3.3 TYPICAL RESPONSE CURVES Typical Accuracy % vs. Frequency @ 100 A, 1 mV/A Output 0.00 % -0.50 % -1.00 % -1.50 % -2.00 % -2.50 % -3.00 % 1 Hz 10 Hz 100 Hz 1000 Hz 10 kHz 100 kHz Frequency Typical Accuracy % vs.
  • Page 16 TYPICAL RESPONSE CURVES (CONTINUED) Typical Phase Shift vs. Frequency @ 200 A, 1 mV/A Output 5¡ 0¡ -5¡ -10¡ -15¡ -20¡ -25¡ 1 Hz 10 Hz 100 Hz 1000 Hz 10 kHz 100 kHz Frequency Current Derating Curve (I < 3000 A) 3000 A 2500 A 2000 A...
  • Page 17: Specifications

    4. SPECIFICATIONS Model 300A 30/300A 1000A 100/1000A Measurement 5 to 300A 5 to 300A 5 to 1000A 5 to 1000A Range Accuracy ±1% +200mA ±1% +200mA ±1% +200mA ±1% +200mA 100mV/A or 10mV/A or Output Signal 10mV/A 1mV/A 10mV/A 1mV/A Crest Factor (mid-range) Phase Shift @...
  • Page 18: Common Specification

    4.1 COMMON SPECIFICATION 4.1.1 Electrical Accuracy: 1% of reading ± residual noise. Frequency Range: 10 - 20,000Hz with current derating. Signal Output: 4.5V max. Working Voltage: 600V CAT IV; 1000V CAT III. Frequency Influence: See Accuracy vs. Frequency curves on pages 16 and 17. Frequency Limitation: See current derating curves (NOTE: no limitation on 300A Range) page 17.
  • Page 19: Mechanical Specifications

    4.1.3 Mechanical Specifications Module Output: Two 4 mm safety banana jacks. Standard 3/4” (19mm) spacing. Battery: 9V Alkaline (NEDA 1604A, IEC 6LR61) recommended. Battery Life: Useable from 9V to 7V, 150 hours typical (continuous use). Low Battery: Power ON indicator (green LED) when battery voltage 7V, LED blinks when battery voltage is low.
  • Page 20: Material Specifications

    4.1.5 Material Specifications Module: UL 94V2, Color dark gray, Polycarbonate. Sensor Latch: Material: Lexan 500R, UL94V0. Cable Assembly to Sensor: UL94V0, 1000V rating. 4.1.6 Safety Specifications Electrical: Double insulation or reinforced insulation between primary or secondary and outer case per EN 61010. ■...
  • Page 21: Maintenance

    5. MAINTENANCE Warning ■ For maintenance use only specified replacement parts. ■ To avoid electrical shock, do not attempt to perform any repair or servie on the instrument unless you are qualified to do so. ■ Do not perform any service while the AmpFlex is on any circuit.
  • Page 22: Repair And Calibration

    If the instrument is returned for calibration, we need to know if you want a standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus recorded calibration data). Ship to: Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ®...
  • Page 23: Limited Warranty

    Service Department (see address below), then return the instrument along with the signed CSA Form. Please write the CSA# on the outside of the shipping container. Return the instrument, postage or shipment pre-paid to: Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ®...
  • Page 24 03/22 99-MAN 100122 v26 Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ® ® 15 Faraday Drive • Dover, NH 03820 USA • Phone: (603) 749-6434 • Fax: (603) 742-2346 www.aemc.com...