7 Remove cable entry points
Only use knockouts
shown
in
shaded
areas.
9 Wiring
Connect using the two way + and - terminals, observing
correct polarity.
Pass the cable through the pre-made entry points.
Cabling can be extended up to 30 m if required, using a closed
electrical connector.
A maximum of one detector is to be fitted to the remote
indicator unit.
Closed electrical
connector
www.emsgroup.co.uk
Detector Base
IDENT
ESS HERE TO
LOG ON
Specification
Operating
temperature
-10 to +55 °C
Storage
temperature
5 to 30 °C
Humidity
0 to 95% non-condensing
Supply
6x AA alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP rating
IP23
Operating
frequency
868 MHz
Output
transmitter
power
Auto adjusting 0 to 14 dB (0 to 25 mW)
Dimensions
(H x W x D)
85 x 85 x 45 mm (remote indicator unit)
Dimensions
(Ø x D)
113 x 40 (detector base only)
Weight
0.15 kg (remote indicator unit)
0.40 kg (wireless detector with detector fitted)
Location
Type A: For indoor use
©2021 EMS Ltd. All rights reserved
8 Fix to the wall
Use suitable fasteners
and fixings.
Use all four mounting
holes.
!
IMPORTANT
Remove dust cover before use.
The device should be tested upon installation and in accordance
with local requirements.
Testing should only be carried out by a fully trained competent
person.
The manufacturer recommends regular functional testing of at
least once per annum or in accordance with local codes of
practice.
Cleaning and repairs must be undertaken by the manufacturers
authorised representative.
Do not open the case to clean inside the detector.
Regulatory information
Manufacturer
Year of manufacture
Certification
Certification body
CPR DoP
Approved to
European Union
directives
Page 2 of 2
40 mm
Carrier Manufacturing Polska Sp. Z o.o. Ul.
Kolejowa 24. 39-100 Ropczyce, Poland
See devices serial number label
10
0905
0359-CPR-0041
EN54-25:2008.Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems.
Part 25: Components using radio links.
EMS declares that this device is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the
following internet address:
www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
TSD033-99 Iss 6 23/11/2021
40 mm
AJM