LUX-PHEBE BOARD
The LUX-PHEBE control board is pre-installed in the PHEBE-SQ operators
for controlling the motor, the limit switches and the courtesy light (fig. 3c).
JP1
1-2
Control of PHEBE-SQ motor by HYDRA board:
1 - motor (BLUE wire)
terminal 16 on HYDRA board
2 - motor (BROWN wire) connection from LUX-PHEBE board to
terminal 17 on HYDRA board
3-4
PHEBE-SQ motor:
3 - motor (BLUE wire)
4 - motor (BLUE wire)
5
not used
6-7
Control of PHEBE-SQ courtesy light by HYDRA board:
6 connection from LUX-PHEBE board to terminal 5 on HYDRA
board
7 connection from LUX-PHEBE board to terminal 18 on HYDRA
board
8
not used
9-10-11 Control of PHEBE-SQ limit switches by HYDRA board:
(only to be used with installation of 2 PHEBE-SQ operators and
1 wall-mounted HYDRA control panel)
9 common connection from LUX-PHEBE board to terminal 13 on
HYDRA board
10 opening limit switches connection from LUX-PHEBE board to
terminal 14 on HYDRA board
11 closing limit switches connection from LUX-PHEBE board to
terminal 15 on HYDRA board
12
not used
13-14-15 Connection of PHEBE-SQ limit switches:
13 common wire
14 opening limit switches
15 closing limit switches
16
not used
NOTE:
In the case where two operators are installed, connect the opening and
closing limit switches of one operator only.
5) MOTOR MOVEMENT CONTROL PARAMETERS
The functional parameters can be changed by means of the incorporated
display programmer or by means of UNIPRO. Here is an explanation of
each option, followed by the setting procedure.
Meaning of the options:
-
Automatic Closing Time (TCA): sets the dwell time with the gate open,
following which the gate is closed again if the TCA function is active.
-
Motor torque (pushing force): regulates the pushing force which is
electronically applied during the opening and closing manoeuvres.
WARNING: Check that the impact force value measured at the
points established by the EN 12445 standard is lower than that
specified in the EN 12453 standard.
Incorrect sensitivity setting can cause injuries to persons or
animals, or damage to things.
-
3-step or 4-step function logic: the Start command modifies the gate
status depending on whether the 3-step or 4-step logic is active, as specified
in the table below. The status of the gate-open warning light is also specified.
GATE STATUS
4 STEPS
gate closed
opens
stops and enters
on opening
tca
(if it is activated)
gate open
closes
stops and does
on closing
not enter tca
after stop
opens
command
-
Impulse lock: activates inhibition of the Start command from pushbutton
and Start command from radio-control device during gate opening.
-
Photocells on opening: if activated, it inhibits the photocells during opening.
In this case, photocell triggering during opening is ignored. Photocell
INSTALLATION MANUAL
connection from LUX-PHEBE board to
GATE-OPEN
3 STEPS
WARNING LIGHT
opens
off
stops and enters
tca
on
(if it is activated)
closes
on
stops and opens
blinks
opens
on
triggering during closing causes the gate to stop and then reopen. If not
activated, photocell triggering on opening causes the gate to stop and
reopen once the obstacle has been removed.
-
Gate-open or 2nd radio channel warning light: if activated, allows you to
connect a 24V
warning light, as in figure 3. In this case the light indicates
the position of the gate as specified in the table above. If not activated, the
output to terminals 21 and 22 shows a current-free and normally open
contact, which is only activated for 2 seconds each time key 2 is pressed
on the associated radio-control device. Key 1 is reserved for the Start
command.
-
Photocells Test: If this setting is not activated (OFF), it inhibits the photocell
checking function, allowing connection of devices not provided with
additional checking contact. In this case, connection to terminal 26 in not
needed (Fig. 3d).
6) PROGRAMMING
6.1) Programming by means of the display
WARNING! To modify the configuration, you need to close jumper J1.
The display programmer available in the board allows you to set all the
HYDRA control panel functions.
Make reference to fig. A and B.
The predefined parameter is shown between square brackets [0].
The writing appearing on the display is indicated between round brackets.
Press the small OK key to display an introduction menu, press OK twice to
bypass this introduction. Now you enter a menu including the following
submenus: Parameters, logics, radio, language, default and autose. In the
first 4 menus you can move up/down within each menu and enter the
submenus, then confirm the values set using the OK key. If you press OK
in the DEFAULT menu, you can reprogram the control unit with the factory-
set values.
To go back and exit the programming function, simultaneously press the up/
down keys several times.
At the end of the configuration, open jumper J1.
6.2) Programming by means of UNIPRO
Connect the UNIPRO programmer to the control unit by means of the
UNIDA accessory (see fig. 4). The HYDRA control unit does not supply the
UNIPRO programmer, which therefore needs an appropriate supply unit.
Parameters menu
-
Automatic Closing Time (TCA) [ 10s ]
Set the numerical value of the automatic closing time from 3 to 60 seconds.
Opening Motor torque (mot torque op) [ 50% ]
-
Set the numerical value of the motor torque between 1% and 99%.
Closing Motor torque (mot torque cl) [ 50% ]
-
Set the numerical value of the motor torque between 1% and 99%.
Zone (zone) [ 1 ] (UNIPRO ⇒ Advanced parameters ⇒ address 1)
-
Set the zone number between a minimum value of 0 and a maximum value
of 127. See paragraph on "Serial connection".
Logics menu
-
TCA (TCA) [ OFF ]
ON
Activates automatic closing
OFF Excludes automatic closing
3 Steps/4Step (3 step) [ OFF ]
-
ON
Enables 3-step logic. stops and reopens
OFF Enables 4-step logic.
Impulse lock (ibl open) [ OFF ]
-
ON
Enables impulse lock during the opening phase.
OFF Excludes impulse lock during the opening phase.
Photocells on opening (photc. open) [ OFF ]
-
ON
Enables on closing phase only.
OFF: Enables on opening and closing phase.
Photocell test (test phot) [ OFF ] (Advanced logics - address 14)
-
ON
Activates the safety device checking function (Fig. 3b)
OFF Deactivates the safety device checking function (Fig. 3d).
Gate-open or 2nd radio channel warning light (sca 2ch) [ OFF ]
-
ON
The output between terminals 21 and 22 is configured as Gate-open
warning light..
OFF The output between terminals 21 and 22 is configured as 2nd radio
channel.
Lock hold (block persist) [ OFF ]
-
ON
This function activates leaf pressure on closing, without this being
considered as an obstacle by the Ampere-stop sensor.
Therefore the leaf continues its travel for another 0.5 sec. after
detecting the closing limit switch.
So by activating the closing limit switches slightly earlier, the leaf will
come to a perfect halt against the backstop.
OFF Movement is exclusively halted by activation of the closing limit