Multidrop Operation; Burst Mode; Units Conversions; Additional Universal Command Specifications - Siemens SITRANS LC500 Operating Instructions Manual

Capacitance transmitters
Table of Contents

Advertisement

MultiDrop operation

The SITRANS LC500 transmitter supports MultiDrop Operation.

Burst mode

The SITRANS LC500 transmitter does not support Burst Mode.

Units conversions

The Transmitter Variable #0 Units are in pF and cannot be changed.
The Transmitter Variable #1 Values may be set to any Units and Value with Command #140.
The Transmitter Variable Range Values may be read at any time with Command #141.
The value returned as Secondary Variable (S.V.) is the result of the following calculation:
TV1 = TV0 Dynamic Range Value in percent x ({TV#1}URV – {TV#1}LRV) + {TV#1}LRV.
This method provides a means of converting TV#0, which is always in pF, to alternative
units (level or volume).

Additional Universal Command Specifications

For a document listing the additional Universal Command Specifications, please contact
Technical Publications at techpubs@siemens-milltronics.com
7ML19985GE04
SITRANS LC500 – OPERATING INSTRUCTIONS
Page 81