Example:
2-state
output
(menu 07)
Device settings:
(The device is first restored to factory settings before being commissioned)
TV0 selected: Transmitter Variable 0 is PV
Lower Range Value (0% of range) is set to 14.3
Upper Range Value (100% of range) is set to 75.8
Current loop is in 2-state mode (C: Hi selected)
2-state fault signalling enabled (F: Hi selected
Activation hysteresis is set to 90
Deactivation hysteresis is set to 8
USL is set to 83.50 pF
LSL is set to 7.3 pF
When the process level reaches 90%, the probe is considered covered and the output will
be 20 mA. If the level exceeds USL, the output will be 22 mA. When the process level
drops to 8%, the probe is considered uncovered, and the output will switch to 4 mA. If the
level drops below LSL, the fault signal will be 22 mA.
1.
F: Hi appears while the button is pressed. See
Page 104
SITRANS LC500 – OPERATING INSTRUCTIONS
Current activated relay module
current loop connection
Active Shield section
(menu 0C) USL
(menu 0F) URV = 100%
Upper Threshold Level = 90%
menu 05 (activation hysteresis)
menu 06 (deactivation hysteresis)
Lower Threshold Level = 8%
Menu 0E LRV = 0%
Menu 0B LSL
Analog Fault Signalling (2-state)
83.5pF
75.8 pF
14.3 pF
7.3 pF
Menu 01 reads Pv = 0
Menu 0E reads 14.30
Menu 0F reads 75.80
Menu 07 reads C:Hi
Menu 08 reads F:Hi
Menu 05 reads 90.0
Menu 16 reads 08.0.
Menu 0C reads 83.50
Menu 0B reads 7.30
on page 67 for more details.