Miscellaneous

Output Signal Processing Test
Displays the Fault/Failure information. If operation is normal, two test displays alternate,
which light up all the LCD segments in a cycle. If there is a fault or failure, an error code is
displayed. See the detailed list of error codes and their meanings, page 53.
Rotary
Menu
Switch
Item
Position
11
1
Set the rotary switch to 1.
To change the state of the output signals, press and hold both buttons simultaneously: the
digital mode outputs (the solid-state switch and the loop-current control in digital mode)
change to their opposite state. Thus 4mA becomes 20mA and contact open becomes
contact closed. This feature allows you to verify that the output signals are properly
processed further on in the PLC/DCS system: if the normal state is non-alarm, changing
the state should generate an alarm.
The outputs stay in the opposite state as long as both buttons are pressed.
Factory Settings
Displays whether the factory settings are still in place, or how much they have been
changed, and allows you to restore the factory settings.
Rotary
Menu
Switch
Item
Position
12
2
Set the rotary switch to 2. To restore the factory settings, press both buttons
simultaneously to change the LCD to 'do it' and hold both buttons for more than one
second. When the buttons are released, the LCD displays FAC A.
7ML19985GE04
Left Arrow
Description
On
Output Signal Processing Test
Left Arrow
Description
Factory Settings
On
SITRANS LC500 – OPERATING INSTRUCTIONS
LCD
Meaning
Display
No parameters
FAC A
changed from factory
setting
Range settings altered:
FAC P
timers and thresholds
unchanged
More parameters have
FAC ?
been changed
Page 73