Range Inversion
Displays whether the device is operating with a normal or inverted range setting.
A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the
LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV
(Menu 0F): the LCD displays inv.
Rotary
Menu
Switch
Item
Position
19
9
1. Set the rotary switch to 9.
2. Press both buttons simultaneously for more than one second to toggle between
the two modes, effectively switching the values for LRV and URV.
Keylock Level
Controls the access protection level for the device. The factory setting is a local
protection level of 0, which places no restriction on modifying settings locally.
Note:
HART settings override local settings:
If the HART setting is 0, there are no restrictions, and you cannot change the
protection to a higher level locally.
If the HART setting is 3, no changes can be made, and this protection level cannot
be changed locally.
Protection level 1 disables the ability to set a value by pressing two buttons
simultaneously.
Protection level 2 disables the ability to change a value by stepping it up or down.
Protection level 3 completely disables all changing of values.
Rotary
Menu
Switch
Item
Position
1F
F
1. Set the rotary switch to F.
2. Press the RED (+) or BLUE (–) button to change the setting.
Page 74
SITRANS LC500 – OPERATING INSTRUCTIONS
Left Arrow
Description
On
Range Inversion
Protection
Left
Arrow
Level
*
0
1
On
2
3
Mode
normal
*
inverted
local
Description
settings
No restrictions
PL 0
No restrictions
Disables 2-button
PL 1
adjustments
Disables 1-button
PL 2
adjustments
Disables all
PL 3
changes
Values
Display shows nor
Display shows inv
Display
HART
settings
PH 0
PH 1
PH 2
PH 3
7ML19985GE04