If the DCS measures the current through the loop compared to a common zero Volt
point, do not ground the negative side of the current loop because measurement
inputs can be short-circuited.
If the DCS measures the current in the positive wire or connector, the negative side
of the current loop can be grounded.
If the DCS has galvanically separated inputs for each measurement channel the
grounding method can be chosen as required.
In hazardous applications a Stahl-type barrier is required, and it is typically mounted on a
DIN rail inside a customer-supplied enclosure located in the non-hazardous area.
Example 1
If no specific Ex conditions apply, the SITRANS LC500 can be directly connected to the
DCS. The supply voltage, however, should remain within the limits set by the
SITRANS LC 500. Connecting a SITRANS LC500 to a DCS does not influence that
equipment. One of the connection cables can be grounded if desired.
GND
COAX
7ML19985GE04
SITRANS LC500 – OPERATING INSTRUCTIONS
Page 33