Do not consider spaces connected by only false ceilings, ductwork or similar
connections as a single space.
If the partition between 2 rooms on the same floor meets certain requirements,
the rooms are considered as one room and the areas of the rooms may be added
up. This way it is possible to increase the room area value used to calculate the
maximum allowed charge.
When considering the smallest single room (for other indoor units only, NOT for
EKVDX), one of the following 2 requirements MUST be followed:
Rooms on the same floor that are connected with a permanent opening that
extends to the floor and is intended for people to walk through can be
considered as one room.
Rooms on the same floor connected with openings that fulfil certain
requirements (see the installation and operation manual of the outdoor unit) can
be considered as a single room. The opening must consist out of at least 2 parts
to allow for air circulation.
3
Specific installer safety instructions
|