Daikin EKVDX-A Installer And User Manual page 15

Vrv system air conditioner
Table of Contents

Advertisement

EKVDX32~100A2VEB
VRV system air conditioner
4P664010-1 – 2021.08
NOTICE
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this unit to guarantee its lifetime. The drying material may
dissolve and damage the system.
NOTICE
Incomplete flaring may cause refrigerant gas leakage.
Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
Electrical installation (see
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from this manual. See
DANGER: RISK OF ELECTROCUTION
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
3
Specific installer safety instructions
|
"17 Electrical
installation" [
"17 Electrical
installation" [
4
 69])
4
 69].
Installer and user reference guide
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ekvdx32a2vebEkvdx50a2vebEkvdx80a2vebEkvdx100a2veb

Table of Contents