Combustion Air Supply Information; Direct Air Supply And Side Wall Venting - Beckett NX Manual

Hide thumbs Also See for NX:
Table of Contents

Advertisement

4.
No other appliance connection should be made to
the same fl ue pipe.
5.
The fl ue pipe should have an upward pitch toward
the chimney of at least 1/4" per foot of length. It
should fi t tightly and should not project into the
chimney.
6.
Any leakage between tiles, around clean-out doors,
or around the vent pipe should be sealed.
INSULATED STAINLESS STEEL CHIMNEY LINERS
The new designs of high effi ciency oil furnaces and
boilers in conjunction with fl ame retention oil burners
are more effi cient. One result of increased effi ciency is
lower fl ue gas temperatures. As fl ue gases rise in the
chimney, they will cool and condense when they reach
the dew point. The condensation will mix with the sulphur
in the fl ue gases creating sulphuric acid. The acid will
attack the chimney mortar, brick and clay liners causing
corrosion, deterioration and blockage of the chimney.
Eventually the blockage could prevent exhausting the
fl ue gases. Instead, the fl ue gases could vent out the
barometric damper into the living space.
Therefore, it is strongly recommended that an approved
insulated stainless steel liner be installed.
For those installations not requiring a chimney, such
as through-the-wall vented appliances, follow the
instructions given by the appliance and power venter (if
used) manufacturers.

Combustion Air Supply Information

Adequate Combustion
and Ventilation Air Supply
Required
Failure to provide adequate air supply could
seriously affect the burner performance and result in
damage to the equipment, asphyxiation, explosion or
fi re hazards.
The burner cannot properly burn the fuel if it is not
supplied with a reliable combustion air source.
Follow the guidelines in the latest editions of the
NFPA 31 and CSA-B139 regarding providing
adequate air for combustion and ventilation.
Appliances located in confi ned spaces
All confi ned spaces should have two (2) permanent
openings; one near the top of the enclosure and one
near the bottom of the enclosure. Each opening must
have a free area of not less than one (1) square inch
per 1,000 BTU's per hour of the total input rating of all
appliances within the enclosure. The openings should
NX Burner Manual
Section: Inspect/Prepare Installation Site
have free access to the building interior, which should
have adequate infi ltration from the outside.
Exhaust fans and other air-using devices
Size air openings large enough to supply all air-using
devices in addition to the minimum size required
for combustion air. If there is any possibility of the
equipment room developing a negative pressure due to
exhaust fans, clothes dryers, etc., either pipe combustion
air directly to the burner or provide a sealed enclosure
for the burner and supply it with its own combustion air
supply.

Direct Air Supply and Side Wall Venting

Connect Outside Air Duct
to NX Adapter
Failure to install adapter properly could
result in impaired combustion, appliance
soot-up, puffback of smoke, and fi re or
asphyxiation hazards.
The outside air adapter must be installed by strictly
following the kit installation instructions.
DO NOT attempt to install outside air piping without
using the outside air adapter and instructions
provided.
Abundant fresh air is required for proper combustion.
Follow the Outside Air Kit
Instructions Exactly
Failure to comply could result in impaired
combustion, appliance soot-up, puffback of smoke,
and fi re or asphyxiation hazards.
Do not attempt to install outside air piping to
the burner without using the outside air kit and
instructions.
For direct vent installations, follow instructions provided
with appliance and direct vent system. Outside
combustion air is required for direct venting.
When installing an NX outside air adapter (Beckett Part
Number 1014U), refer to the instruction sheet supplied
with the adapter. This kit allows combustion air to be
piped directly to the burner. The NX outside air adapter
kit may also be used for chimney vent applications that
require outside combustion air.
Clearances to burner and appliance
Provide space around burner and appliance for easy
service and maintenance.
Check minimum clearances against those shown
by the appliance manufacturer and by applicable
building codes.
7

Advertisement

Table of Contents
loading

Table of Contents