Combustion Air Supply; Directlsidewall Venting Application; Fuel Line Installation; Fuel Line Valves And Filters - Beckett NX50LG Manual

Nx series oil burner
Table of Contents

Advertisement

• Combustion
Air Supply
Information
See NFPA Standard 31 for complete details.
Appliances
located
in confined
spaces:
All
confined spaces should have two (2) permanent
openings; one near the top of the enclosure and
one near the bottom of the enclosure. Each open-
ing must have a free area of not less than one (1)
square inch per 1,000 BTU's per hour of the total
input rating of all appliances within the enclosure.
The openings should have free access to the build-
ing interior, which should have adequate infiltration
from the outside.
Exhaust
fans and other air-using
devices:
Size
air openings
large enough to supply all air-using
devices in addition to the minimum size required
for combustion air. If there is any possibility of the
equipment
room developing
a negative pressure
due to exhaust fans, clothes dryers, etc., either pipe
combustion air directly to the burner or provide a
sealed enclosure for the burner and supply it with
its own combustion air supply.
• Direct/Sidewall
Venting Application
Connect
Outside Air Duct
to NX Adapter
to
install
adapter
properly
could result
in impaired
combustion,
appliance
soot=up,
puffback
of smoke,
and fire or asphyxiation
hazards.
The outside air adapter must be installed by strictly
following the kit installation instructions.
DO NOT attempt to install outside air piping without
using the outside air adapter and instructions
pro-
vided.
Abundant
fresh air is required for proper combus-
tion.
Failure
For direct vent installations, follow instructions pro-
vided with appliance and direct vent system.
Out-
side combustion air is required for direct venting.
When installing an NX outside air adapter (Beckett
Part Number 1014U), refer to the instruction sheet
supplied with the adapter. This kit allows combus-
tion air to be piped directly to the burner. The NX
outside air adapter
kit may also be used for chim-
ney vent applications that require outside combus-
tion air.
Inspect/Prepare
installation
Site
• Fuel Line installation
CAUTION
Do Not Use Teflon Tape
Damage
to the pump could cause impaired
burn=
er operation,
oil leakage
and appliance
soot=up.
Never use Teflon tape on fuel oil fittings.
Tape fragments can lodge in fuel line components
and fuel unit, damaging the equipment and pre-
venting proper operation.
Use oil-resistant pipe sealant compounds.
Route the fuel line through the opening in the bottom
of the burner cover. Continuous
lengths of heavy
wall copper tubing are recommended. Always use
flare fittings. Never use compression fittings.
Always
install fittings in accessible
locations. To
avoid vibration
noise, fuel lines should not run
against the appliance or ceiling joists.
Fuel Line Valves and Filter
Install two high quality fusible-handle design shutoff
valves in accessible locations on the oil supply line
to comply with the NFPA31 Standard. Locate one
close to the tank and the other close to the burner,
upstream of the filter.
Install a generous capacity filter inside the building
between the fuel tank shutoff valve and the burner,
locating both the filter and the valve close to the
burner for ease of servicing.
Filter should be rated
for 50 microns or less.
To further protect the fuel supply system and re-
duce nozzle orifice plugging with firing rates below
0.75 gph, a dual filtration system can be installed.
This typically consists of a 50 micron primary filter,
located near the fuel tank and a secondary filter rat-
ed for at least 10 microns located near the burner.
RWB 6104 BNX R02
Page 5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents