Professional Installer's Responsibility; Pre-Installation Checklist; Indoor Installation; Combustion Air Supply - Beckett CG15 Manual

Gas burner
Hide thumbs Also See for CG15:
Table of Contents

Advertisement

Professional Installer's Responsibility

Follow these instructions
exactly
Failure to follow these instructions could
lead to equipment malfunction and result
in asphyxiation, explosion or fi re.
Please read all instructions before proceeding. Follow
all instructions completely.
This equipment must be installed, adjusted, and
started by a qualifi ed service agency that is licensed
and experienced with all applicable codes and
ordinances and responsible for the installation and
commissioning of the equipment.
The installation must comply with all local codes and
ordinances having jurisdiction and the latest edition of
the National Fuel Gas Code ANSI Z223.1 (NFPA 54)
and CAN1-B149.1 in Canada.
Concealed damage – If you discover
damage to the burner or controls
during unpacking, notify the carrier at once and fi le the
appropriate claim forms.
High altitude installations – Accepted industry practice
requires no derate of burner capacity up to 2000 feet
above sea level. For altitudes higher than 2000 feet,
derate the burner capacity 2% for each 1000 feet above
the 2000 feet.
50 Hz motors – The burner ratings, air settings and other
adjustments are based on 60 Hz motors at 3450 rpm.
Derate fi ring capacity 20% when using 50 Hz motors.
Consult factory for specifi c application data.

Pre-installation Checklist

Indoor Installation

Protect against Dust and
Moisture
Wet or dusty environments could lead to blocked air
passages, corrosion damage to components, impaired
combustion performance and result in asphyxiation,
explosion or fi re.
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or
sprayed liquids.
Keep the installation clear of dust, dirt, corrosive
vapors, and moisture.
Protective covers and more frequent maintenance
may be required.
CG15, CG25, CG50 Burner Manual
Section: Pre-installation Checklist

Combustion Air Supply

The burner requires combustion air and ventilation air
for reliable operation. Assure that the building and/or
combustion air openings comply with the latest edition of
the National Fuel Gas Code ANSI Z223.1 (NFPA 54).
For appliance/burner units in confi ned spaces, the room
must have an air opening near the top of the room, plus
one near the fl oor, each with a free area at least one
square inch per 1000 Btu/hr input for all fuel-burning
equipment in the room.
For Canadian installations, refer to latest edition of CAN1-
B149.1 standard.
If there is risk of the space being under negative pressure,
or of exhaust fans or other devices depleting available
air for combustion and ventilation, the appliance/burner
should be installed in an isolated room provided with
outside combustion air.

Clearances

With the burner installed in the appliance, there must be
adequate space in front of and on the sides of the burner
to allow access and operation. Verify that the clearance
dimensions comply with local codes and with the appliance
manufacturer's recommendations.

Fuel Gas Supply

Verify that the gas supply piping complies with all applicable
local codes and the latest edition of the National Fuel Gas
Code ANSI Z223.1 (NFPA 54).
Insure that the supply gas pipe size is capable of providing
at least the minimum pressure required to the burner gas
train inlet at the burner's full capacity rating. Refer to
Table 1.

Flue Vent System

The fl ue gas vent system must be in good condition
and must comply with National Fuel Gas Code ANSI
Z223.1 (NFPA 54) and all other applicable codes having
jurisdiction for vent construction, capacity, and sizing.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cg25Cg50

Table of Contents