Table of Contents

Advertisement

3.4
Connection to the
Internet
Default ports for
communication
LAN interface
WAN interface
WLAN interface
Leica ComGate10, Operation

Connections

Internet network available
Connect WAN on the ComGate10 with an
Ethernet cable to the Internet.
Instruments connected to the ComGate10 can be inserted in GeoMoS Monitor
- Sensor Manager.
The default ports for connecting an instrument by the serial or USB port are:
• Serial port:
• USB port:
• Serial port (serial2USB):
• Configuration port:
• Port LAN:
• Port LAN:
If an Internet connection is established by WAN and mobile Internet then the WAN
connection is preferred. If the WAN connection gets lost then the mobile Internet
switches on immediately. If the WAN connection is working again then the Internet
connection is established again over the WAN.
By default, the ComGate10 is used as a Dynamic Host Configuration Protocol (DHCP)
server:
IP address:
Subnet mask:
When connecting another device to the LAN interface, the device gets an IP address
automatically.
The ComGate10 can be used as a Domain Name System (DNS) server.
The WAN interface is used as a DHCP client by default and obtains an IP address. This
port is used for the connection to an existing network with Internet access.
The WLAN interface can act as an access point and therefore provide IP addresses to
clients or act as client and connect to an existing WLAN. By default the WLAN interface
is disabled.
The number of attached antennas can be configured over the web interface of the
ComGate10. If only one antenna is used, it must be attached to WLAN1. However, for
better diversity and thus better throughput and coverage, it is highly recommend using
two antennas.
The settings for LAN, WLAN and WAN can be changed over the web user interface of
the ComGate10. Ask your IT administrator for support if you want to change some
settings.
Internet network unavailable
Use a mobile connection to the Internet.
Receive the public IP address from the
mobile provider in order to connect
GeoMoS monitor to a sensor.
50001
50006
50005
50050
50031
Forwarded to 192.168.1.31:80
Example WebCam
50032
Forwarded to 192.168.1.32:80
192.168.1.1
255.255.255.0
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comgt10lweu

Table of Contents