2.Writing data structure
2.1.2 Momentary Set
The action when the button is released/pushed changes according to 'Not Used'/'Used'
for the 'Momentary Set' in PB2p/PB4p/PB8p.
The following table shows the status of the bits for changed items and the bits of
operation status.
Momentary Set
Not Used
Not Used
Used
Used
When the 'Momentary Set' is 'Not Used', an application in MODBUS/TCP Server will
process for FRO and set OFF(0) in RFO and FO after it completes.
When the 'Momentary Set' is 'Used', an application in MODBUS/TCP Server processes
network disconnection etc.
During momentary, a timer should be used to prevent the buttons from staying in a
pushed state.
6
Table 2.1 Momentary Set
Operation
Push a button
Release a button
Push a button
Release a button
Bit of changed items
-
ON(1)
ON(1)
ON(1)
Bit of operation status
-
ON(1)
ON(1)
OFF(0)