Refrigerant charging

Insulating the pipe located inside of the
outdoor unit
• With a pipe insulator, insulate the pipe up to whole service
valve located inside of the outdoor unit.
• Seal the gap between the outdoor unit pipe and the insulator.
Rainwater and dewdrops may soak through the gap between
the pipe and the insulation of the outdoor unit installed on the
outside.
• Separate the cover of the pipe and close it after insulation
work. Only remove a knock-out hole cover where the pipe
will be installed. If the knock-out hole is open unnecessarily,
it must be closed. If not, small animals such as squirrels and
rats may get into the unit through the hole and the unit may
be damaged.
Refrigerant charging
• The R-410A refrigerant is blended refrigerant. Add only liquid
refrigerant.
• Measure the quantity of the refrigerant according to the length
of the liquid side pipe. Add quantity of the refrigerant using a
scale.
Important information: regulation
regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do not vent
gases into the atmosphere.
WARNING
• Inform user if the system contains 5 tCO₂e or more of
fluorinated greenhouse gases. In this case,
it must be checked for leakage at least once every 12 months,
according to regulation No. 517/2014. This activity must be
covered by qualified personnel only. In the case of the situation
above, the installer (or authorized person with responsibility
for final check) must provide a maintenance book, with all
the information recorded, according to REGULATION (EU)
No. 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 16 April 2014 on fluorinated greenhouse gases.
Please fill in the following with indelible ink on the refrigerant
charge label supplied with this product and on this manual.
: The factory refrigerant charge of the product.
: The additional refrigerant amount charged in the field.
+
: The total refrigerant charge.
50
English
H/P
H/R
Indoor unit
Unit
, a
, b
+ , c
Refrigerant type
R-410A
• GWP=Global Warming Potential
• Calculating tCO
e : kg x GWP / 1000
2
NOTE
a Factory refrigerant charge of the product: see unit name plate.
b Additional refrigerant amount charged in the field. (Refer
to the above information for the quantity of refrigerant
replenishment.)
c Total refrigerant charge.
d Refrigerant cylinder and manifold for charging.
d
Outdoor
unit
tCO₂e
Kg
GWP value
2088