The R-410A refrigerant is blended refrigerant. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the refrigerant
using a scale.
Charging refrigerant
Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant.
If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and liquid
side service valve. Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor PCB.
R-410A (Inject
liquid refrigerant)
Scale
Open the gas side and liquid side service valve completely after charging the refrigerant. (If you operate the air
conditioner with the service valve closed, the important parts may be damaged.)
CAUTION
Put on safety equipment when charging refrigerant.
Do not charge the refrigerant when you adjust or control other product such as indoor units or EEV kits.
When the ambient temperature is low in winter time, do not heat the refrigerant container to speed up the charging
process. There is risk of explosion.
Beware for possibility of refrigerant leakage when you connect the manifold gauge to the charging port for heating.
Close the valve of the refrigerant container immediately after charging the refrigerant. If not, there might be a change
in entire amount of refrigerant.
Outdoor unit
Gas side
Liquid side
Manifold gage
Vacuum port
Service valve