Installation posi-
tion
28
The inverter is suitable for outdoor installation.
Because of its IP 65 protection class, the inverter is resistant to
water jets from any direction and can also be used in damp en-
vironments.
The inverter is suitable for outdoor installation.
To keep the heating of the inverter as low as possible, it is better
not to expose the inverter to direct sunlight. Mount the inverter
in a protected location, for example below the solar modules or
under a roof overhang.
IMPORTANT! The inverter must not be installed or used at alti-
tudes above 4000 m.
Do not install the inverter in:
-
Areas where it may be exposed to ammonia, corrosive gases,
acids or salts (e.g. fertiliser storage areas, vent openings for
livestock stables, chemical plants, tanneries, etc.)
Due to the noise generated by the inverter under certain operat-
ing conditions, it should not be installed close to living areas.
Do not install the inverter in:
-
Areas where there is an increased risk of accidents from
farm animals (horses, cattle, sheep, pigs, etc.)
-
Stables or adjoining areas
-
Storage areas for hay, straw, chaff, animal feed, fertilizers,
etc.
-
Storage or processing areas for fruit, vegetables or viticul-
ture products
-
Areas used in the preparation of grain, green fodder or an-
imal feeds
The inverter is designed to be dust-tight (IP 65). However, in
areas with high dust accumulation, the cooling surfaces may col-
lect dust and this may impair the thermal performance. In such
cases, regular cleaning is required. Consequently, we do not re-
commend installation in places and environments with strong
dust formation.
The inverter is designed to be installed vertically on a vertical
wall. The optional floor racks must not be used for vertical
mounting.