Channels / power used
Modulation
Tauro Eco 99-3-
Input data
D / 99-3-P
Maximum input voltage
(at 1000 W/m²/ -10 °C in an open circuit)
Start-up input voltage
MPP voltage range
Number MPP-controller
Maximum input current (I
P-version PV1 / PV2
D-version PV1 / PV2 / PV3
per string (for D-version only)
Max. short circuit current (I
P-version total
D-version total
PV1 / PV2 / (PV3 for D-version only)
per string (for D-version only)
Maximum PV field power (P
P-version PV1 / PV2
D-version PV1 / PV2 / PV3
DC overvoltage category
Max. inverter backfeed current to the array
P-version total
D-version total
Max. capacity of the PV generator against earth
PV array to earth insulation resistance setup value
PV array to earth insulation resistance adjustable
range
Sudden change residual current limits and re-
sponse times
Continuous current limits and response times
Continuous current limits adjustable range
PV array insulation test timer
94
) Total
DC max
= I
)
SC PV
SC max
) Total
PV max
3)
Channel: 1-11 b,g,n HT20
Channel: 3-9 HT40
<18 dBm
802.11b: DSSS (1Mbps
DBPSK, 2Mbps DQPSK,
5.5/11Mbps CCK)
802.11g: OFDM (6/9Mbps
BPSK, 12/18Mbps QPSK,
24/36Mbps 16-QAM,
48/54Mbps 64-QAM)
802.11n: OFDM (6.5
BPSK, QPSK, 16-QAM,
64-QAM)
1000 V
650 V
580 - 930 V
175 A
100 A / 100 A
75 A / 75 A / 75 A
14.5 A
250 A
355 A
125 A / 125 A / 125 A
20 A
150 kWp
79 kWp / 79 kWp
57 kWp / 57 kWp / 57
kWp
125 A
250 A
19998 nF
34 kΩ
10 - 10000 kΩ
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
900 / 300 mA / ms
30 - 1000 mA
24 h
DC
DC
DC
1
2
4)
4)