Requirements for Use

 Requirements for hot/cold water supply
Water for use
Pressure of hot/
cold water supply
Temperature of
hot water supply
 Floor
Make sure that the floor is level.
Make sure that the installation area is flat and free of irregularities.
Use floor panels with high water resistance.
Raising pipes
Cold/Hot water
supply
Drain
In the case where the floor is finished with tiles etc., screwing bolts into the floor
surface when installing the shampoo unit may cause a crack on the floor surface.
Change the material of the floor of the installation area to plywood, mortar, etc.,
referring to the product layout drawing and the pattern paper.
* The floor panel must have the strength as shown below.
Wooden floor
Mortar floor
Special floor
(stone etc.)
Waterproofing
• In case of the installation on the second floor or higher, waterproof the floor
appropriately.
• Drinking water (Non-drinkable well water, or water including sand or rust are not
approved for use.)
• If the water hardness is 80 ppm or more, treat the water with a water softener in
order to prevent scale clogging of the equipment.
• Set the pressure within the range from 0.08 MPa to 0.6 MPa (0.8 to 6 kgf/cm
• When the pressure exceeds 0.2 MPa (2 kgf/cm
pressure reducing valve" type.
• The cold water supply pressure must be equal to or higher than the hot water
supply pressure.
• The difference between the cold water supply pressure and the hot water
supply pressure must be 0.2 MPa (2 kgf/cm
• The temperature of hot water supply must be at least 10˚C higher than that of
hot water from the shower.
Rc1/2" Floor raising pipe
Raising height: Hot water supply 80 mm, Cold water supply 110 mm
VU40 Floor raising pipe Raising height: 90 mm
strength of plywood of 30 mm thickness or more
strength of mortar of 50 mm thickness or more
a base with the strength equivalent to the above must be installed at the
installation position.
2
) or less.
2
3
), select the floor unit "with
).
2