Mitsubishi Electric MCF-C13UV-E1 Service Manual page 27

Wireless type
Table of Contents

Advertisement

9-3. DRY (
) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room temperature
and determines the set temperature. Set temper-
ature is as shown on the right chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY mode of
"I FEEL CONTROL".
(4) DRY operation will not function when the room
temperature is 13°C or below.
9-4. FAN (
) OPERATION
(1) Press the OPERATE/STOP (ON/OFF) button.
(2) Select FAN mode with the OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
9-5. AUTO VANE OPERATION
(1) Vane motor drive
This series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by pulse signals (approx. 12V, transmitted from indoor microprocessor.)
(2) Each time the VANE CONTROL button is pressed, angle of horizontal vane is changed in sequence, from 1, 2, 3, 4, 5,
SWING to AUTO.
(3) Positioning
The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER ON/OFF).
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
1
2
3
4
5
AUTO
SWING
27

Advertisement

Table of Contents
loading

Table of Contents