COMMISSIONING
Setting not required.
INV1
Setting before shipment
ON
1 2 3 4 5 6
N O T E
11 COMMISSIONING
11.1 PRELIMINARY CHECKS
The test run must be carried out according to the instructions
given in chapter
D A N G E R
Make sure the refrigerant pipes and communication cables
between the outdoor and indoor units are connected to the
same refrigeration cycle. Failure to do so could lead to abnormal
operations or a serious accident. Check that the setting of the
refrigerant cycle DSW switches (DSW1 and RSW1 on outdoor
units, DSW5 and RSW2 on indoor units) and of the unit number
of the indoor units is suitable for the system. Check whether
indoor and outdoor units is correct. Pay particular attention to
the outdoor unit nunber, the refrigerant cycle number and the
terminal resistance.
measuring the resistance between the ground and the terminal
of the electrical components. If not, do not use the system until
the electrical leak has been detected and repaired. Do not apply
voltage to the communication terminals.
Check that all cables, L1, L2, L3 and N (R, S, T and N) are
correctly connected to the power line. If they are not correctly
connected, the unit will not work and the remote control will
indicate alarm code "05". When this occurs, check and change
the power line phase according to the sheet attached to the rear
of the service cover.
C A U T I O N
The FSXNSE and FSXNPE series outdoor units do not work
for 4 hours after the power supply line has been connected
(stoppage code d1-22). Where the unit is to be started within 4
hours, release the protection control as follows:
1 Switch on the power supply to the outdoor unit.
2 Wait 30 seconds.
55
PMML0479 rev.2 - 02/2018
INV2
Setting before shipment
ON
1 2 3 4 5 6
3 Press PSW5 on the outdoor unit PCB for more than 3
.
seconds to release code d1-22. Where a remote control is
used for releasing, press Air Flow and Auto Louver at the
same time for 3 seconds.
Where several base units are combined, stick the label on the
main unit in a visible place (outdoor unit 1) so that the outdoor
secondary unit (outdoor units 2 and 3).
C A U T I O N
1
2
N O T E
Cancellation of current detection
ON
1 2 3 4 5 6