ELECTRIC WIRING
9.1.1 Installation position of the optional
Installation position (example: RAS-10FSXNPE, lower and side
views).
A
Drain pipe
B
Optional drain plug
10 ELECTRIC WIRING
10.1 GENERAL INFORMATION
C A U T I O N
10.2 GENERAL VERIFICATIONS
1 Make sure the electric components in the installation (earth
leakage breaker, circuit breaker, cables, connectors, cable
terminals and main power switches) have been selected
correctly in line with the electrical data given in this Manual.
Also make sure that these components are compliant with
national and local codes.
a. The electricity supply to the unit should be via an
exclusive power control switch and protective circuit
national safety regulations.
b. Connect the power supply wiring for each group of indoor
units to its outdoor unit group (maximum capacity for each
47
PMML0479 rev.2 - 02/2018
C
D
Base of unit
Material/
Model
Description
colour
Drain boss
PP/black
DBS-
Drain cap
PP/black
TP10A
Rubber cap
CR/black
Model
Standard type
8-18
20-36
38-40
42-48
50-54
56 - 60
62 - 66
DBS-TP10A
68 - 72
74 - 78
80 - 84
86 - 90
92 - 96
D A N G E R
group of indoor units: 26 HP). Do not mix units of different
groups.
c. For heat recovery systems, the CH unit and the indoor
unit of the same refrigerant cycle can be supplied from the
same mains power switch.
2
rated voltage. Where the voltage capacity is too low, it will not
be possible to start the system due to the drop in voltage.
3 Sometimes, the refrigeration/heating system is not able to
operate correctly in the following cases:
When the system is supplied from the same supply line as
other major consumers (heavy machinery, power inverter
Qty
Application
Connecting for Drain
2
Piping
Embolization for Drain
2
Hole
Sealing for Boss and
4
Cap
Q´ty
type
5-14
1
16-24
2
26-32
3
34/36
4
38-42
3
44/46
4
48/50
5
52/54
6
56/ 58
5
60
6
62
7
64 - 72
8