2.4

CLEARANCES

Install the VS-686SS5 vertically and allow sufficient clearances for effective cooling as shown in Fig.
5.
Fig. 5 Clearances
NOTE
1.
2.
3.
4.
5.
6.
*
50 mm or more
30 mm or more
30 mm or more
*
50 mm or more
(a) Front View
The clearances required at top/bottom and both sides are common in open chassis type
(IP00) and enclosed wall-mounted type (IP20).
Remove the top and bottom covers to use the open chassis type of 15kW or less.
When installing the models of 30kW or more equipped with eyebolts, extra spacing will
be required on either side. For detailed dimensions, contact your YASKAWA representa-
tive.
For the external dimensions and mounting dimensions, refer to APPENDIX 2 "DIMEN-
SIONS."
Allowable intake air temperature to the inverter:
Open chassis type
Enclosed wall-mounted type : -10_C to +40_C
Ensure sufficient space for the sections at the upper and lower parts marked with ∗ in order
to permit the flow of intake/exhaust air to/from the inverter.
120 mm or more
120 mm or more
(b) Side View
: -10_C to +45_C