T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 8
UV based anti-bacterial systems may damage return (e.g. louvered door). Therefore, filter rails are the coated air coils. industry standard and are included on Johnson Controls commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
(e.g. louvered door). Therefore, filter rails are the industry standard and are included on Johnson Controls commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
Page 12
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Vertical Installation, Cont’d.
Optional pressure-rated hose assemblies designed (0.6m Length Standard) transmitted through the hoses to the structure, causing specifically for use with Johnson Controls units are available. unnecessary noise complaints. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings Figure 11: Supply/Return Hose Kit at one end to prevent kinking during installation.
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 15
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Variable Water Flow Heat Pump Applications Overview, Cont’d.
Page 16
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Variable Water Flow Heat Pump Applications Overview, Cont’d.
Johnson Controls recommends unit insulation any time the To ensure proper maintenance and servicing, P/T ports are water temperature is expected to be below 60ºF (15.6ºC).
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 21
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Ground-Water Heat Pump Applications, Cont’d.
20 mesh] size. The Johnson Controls Water Quality Table provides water quality requirements for Johnson Controls coaxial heat exchangers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water.
Sensor (Optional) the wall so that it appears level and so the thermostat with Johnson Controls units, provided it has the correct Remote Indoor wires protrude through the middle of the back plate. Mark number of heating and cooling stages.
Airflow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fiberglass filter. Condenser hot water reheat equipped units are factory set to operate in stage 2 airflow. JE-Series with Condenser Hot Water Reheat All JE units have an ECM fan motor. The small amount...
NOTE: Not all units have two-stage heating (dehumidification), and heating. The cooling/heating functionality. modes are like any other Johnson Controls WSHP. The reversing valve (“O” signal) is energized in cooling, along • Reheat Mode: A call from the Humidistat/Dehumidistat with the compressor contactor(s) and blower relay.
Page 44
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Condenser Hot Water Reheat Option, Cont’d.
Page 45
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Condenser Hot Water Reheat Option, Cont’d.
Closed Closed 4. Verify that all strainers are in place (Johnson Controls recommends a strainer with a #20 stainless steel wire mesh). Start the pumps, and systematically check each vent to ensure that all air is bled from the system.
Check for warm air delivery within a few minutes 5. Two factors determine the operating limits of after the unit has begun to operate. Johnson Controls heat pumps, (a) return air temperature, and (b) water temperature. When any d. Refer to table 9. Check the temperature of both one of these factors is at a minimum or maximum entering and leaving water.
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 52
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Unit Operating Conditions, Cont’d.
Page 53
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Unit Operating Conditions, Cont’d.
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 59
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Functional Troubleshooting, Cont’d.
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1...
Page 61
Reduced water flow Plugged strainer or filter - clean or replace in heating JE-Series Check water flow adjust to proper flow rate I s s u e D a t e : M a y 1 0 , 2 0 2 1...
W A T E R - S O U R C E H E A T P U M P S JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Start-Up Log Sheet Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM.
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Date: ________________________ Packaged Unit Refrigeration Schematic JE-Series I s s u e D a t e : M a y 1 0 , 2 0 2 1 Customer: _____________________________________ Antifreeze: ________________________...
97B0075N19 Johnson Controls works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact Johnson Controls’ Customer Service Department at 1-877-329-7430 for specific information on the current design and specifications.