Condensate Drain Siphon Cleaning - Beretta POWER MAX Installation And Operation Manual

Condensation heating module
Table of Contents

Advertisement

3.12.1 Condensate drain siphon cleaning

For models POWER MAX 50 P DEP and POWER MAX 50 P:
- Remove the front panel from the boiler and locate the conden-
sate discharge syphon (1)
2
- Remove the split pin (2), detach the corrugated condensate
drain hose, and remove the siphon. Unscrew the two caps (3)
to disassemble the siphon
- Remove the float (4) and clean all internal components.
Once the maintenance operations are complete, refit the compo-
nents working in the opposite direction of what was described.
b
Fill the siphon with water before you start up the boiler to pre-
vent combustion gases escaping into the room during the first
few minutes of boiler functioning.
For models POWER MAX 65 P, POWER MAX 80 P, POWER MAX 100,
POWER MAX 110, POWER MAX 130, POWER MAX 150 (accessory):
1
3
4
3
Once the maintenance operations are complete, refit the compo-
nents working in the opposite direction of what was described.
b
- Locate the condensate drain trap (1), mounted under the ap-
pliance.
- Loosen the clamp (2), detach the condensate drainage corru-
gated tube (3), remove the siphon and remove it using the two
screw plugs (4)
- Remove the float and clean all internal components.
3
2
Fill the siphon with water before you start up the boiler to pre-
vent combustion gases escaping into the room during the first
few minutes of boiler functioning.
1
4
4
59