3.10 Control board replacement

b
System configurations must be performed only by the Tech-
nical Assistance Centre or by personnel authorized by
When replacing the front control panel, at subsequent restart, the
system performs a consistency check between the configuration
data saved on the Master board and those saved in the user inter-
face; therefore, when replacing the control interface, check Par.9097,
Par.9098 and Par.2116.
Change the parameter Par.9097, setting the value according to the
following table:
Model
POWER MAX 50 P DEP
POWER MAX 50 P
POWER MAX 65 P
POWER MAX 80 P
POWER MAX 100
POWER MAX 110
POWER MAX 130
POWER MAX 150
b
(*) Factory setting. It may be necessary to change the value
depending on the type of installation and the accessories in-
stalled.
Change the parameter Par.9098, setting the value according to the
following table:
Model
POWER MAX 50 P
DEP
POWER MAX 50 P
54
POWER MAX 65 P
POWER MAX 80 P
POWER MAX 100
POWER MAX 110
POWER MAX 130
POWER MAX 150
Check the settings for parameter 2116:
Model
POWER MAX 50 P DEP
POWER MAX 50 P
POWER MAX 65 P
POWER MAX 80 P
POWER MAX 100
POWER MAX 110
POWER MAX 130
POWER MAX 150
Par. 9097
46 (*)
46 (*)
1 (*)
1 (*)
1 (*)
1 (*)
1 (*)
1 (*)
methane
Par. 9098
methane
21
LPG
22
methane
19
LPG
20
methane
11
LPG
12
methane
9
LPG
10
methane
7
LPG
8
methane
5
LPG
6
methane
3
LPG
4
methane
1
LPG
2
Par. 2116
3
3
0
0
0
0
0
0

3.11 Maintenance

It is mandatory to perform maintenance and cleaning of the device at
least once a year.
.
B
b
The non-performance of the annual maintenance will invalidate
the warranty.
This operation, carried out by Technical Assistance Centre or by pro-
fessionally qualified personnel, is necessary to monitor and ensure
that the flue pipes inside and outside of the device, the fan, the safety
valves, the condensate removal devices, the water drainage tubes
and all the measurement and control devices are in perfect working
order.
Table of the compulsory maintenance activities (to be per-
formed every 2000 working hours or at least once a year)
Make the combustion test
Check the conditions of the inlet pipes (if present) and the flue
pipes by making sure that no leakage is present
Check the ignition electrode
Clean the combustion chamber and check the conditions of the
gaskets you have dismantled during such operation
Clean the condensate discharge pipe
Check the parameters settings
Check if there is any gas leakage
Check if there is any leakage on the hydraulic connections
Check the integrity of the cabling system and its related connec-
tions
Make sure the ignition takes place regularly
Make sure that there is the flame after ignition
Check the safety devices down the equipment
Check the system pressure
b
Before carrying out any maintenance or cleaning, disconnect
the power from the device by turning off the bipolar main switch
and closing the main gas valve. In addition, for all maintenance
(to be carried out at least once a year, as noted above) always
replace all the flue and gas seals, in particular the burner seals.
Before performing any operation:
- disconnect the electric power supply by turning the main sys-
tem switch to "off"
- close the gas shut-off valve.