1.9 Water circuit

1
5
4
3
2
RI
Heat exchanger
1
Circulator (only for models POWER MAX 50 P DEP -
2
POWER MAX 80 P)
Drain cock
3
Minimum pressure switch
4
NTC return probe
5
NTC delivery probe
6
Safety thermostat temperature sensor
7
Automatic bleed valve
8
Flow-meter
9
Central heating flow
MI
Central heating return
RI
Values of NTC probes' resistors with changing temperatures.
Temperature °C
Tolerance test
Resistor Ω
±10%
-40
191908
-35
146593
-30
112877
-25
87588
-20
68471
-15
53910
-10
42739
-5
34109
0
27396
5
22140
10
17999
15
14716
20
12099
25
10000
30
8308
35
6936
40
5819
6 7 8
9
MI
Temperature °C
Tolerance test
Resistor Ω
±10%
45
4904
50
4151
55
3529
60
3012
65
2582
70
2221
75
1918
80
1663
85
1446
90
1262
95
1105
100
970
105
855
110
755
115
669
120
594
125
529

1.10 Positioning the temperature sensors

Probes placed on the related sockets of the thermal module
(POWER MAX 50 P DEP - POWER MAX 50 P):
Exhaust flue probe
1
Safety thermostat
2
CH flow temperature sensor
3
Return probe
4
2
4
1
Front view
Probes placed on the related sockets of the thermal module
(POWER MAX 65 P ÷ POWER MAX 150):
Exhaust flue probe
1
Safety thermostat
2
CH flow temperature sensor
3
Return probe
4
Front view
3
Side view
3
2
4
1
Side view
1
13
3
2
1