3.4 Error List

When a display has a technical fault, a numeric error code appears that will enable the maintenance operator to identify the possible cause.
There are 3 categories of errors:
1
Permanent: errors that require a manual reset
2
Temporary: errors that are automatically reset once the cause that generated them is removed or stopped
3
Notices: simple warnings that do not block the appliance's operation
3.4.1

Permanent Errors

Nr. Error
Description
E2PROM_
0
READ_ER-
Internal software error
ROR
Three unsuccessful ignition
1
IGNIT_ERROR
attempts in a row
GV_RELAY_
Failure detected in the GV
2
ERROR
(Gas Valve) relay
SAFETY_RE-
3
Internal control board error
LAY_ERROR
BLOCKING_
Control had a blocking er-
4
TOO_LONG
ror for more than 20 hours
FAN_ERROR_
Fan is not running for more
5
NOT_RUN-
than 60 seconds
NING
FAN_ERROR_
Fan runs too slow for more
6
TOO_SLOW
than 60 seconds
FAN_ERROR_
Fan runs too fast for more
7
TOO_FAST
than 60 seconds
8
RAM_ERROR Internal software error
WRONG_EE-
Contents of Eeprom is not
9
PROM_SIG-
up to date
NATURE
E2PROM_ER-
Wrong safety parameters
10
ROR
in Eeprom
STATE_ER-
11
Internal software error
ROR
12
ROM_ERROR Internal software error
The external overheat
protection is enabled
MAX_TEMP_
15
or the T_Supply sensor
ERROR
measures a temperature of
over 100°C (212°F)
Flue temperature exceed-
FLUE_GAS_
16
ed the maximum flue
ERROR
temperature
STACK_ER-
17
Internal software error
ROR
INSTRUC-
18
TION_ERROR Internal software error
ION_CHECK_
19
Internal software error
FAILED
Flame still present 10
FLAME_OUT_
20
seconds after closing the
TOO_LATE
gas valve
Checks
Check gas supply pressure
Check ignition spark
Correct amount of air
Check for voltage at the gas valve
Check the integrity of the wire connections
between gas valve and control board
Press RESET button to display the Block-
ing error description
Check that the fan is connected to the
power supply
Check PWM connection of the fan
Check the pump to verify the flow circu-
lation
Check if the valves on hydraulic circuit are
open
Check the safety thermostat
Solutions
Control board replacement
If the gas supply pressure is incorrect, it
must be adjusted to the correct pressure
If spark is not present check for correct
ignition electrode position
If the combustion air pressure is incorrect,
inspect the vent system and eliminate any
obstructions
If the voltage at the gas valve is not the
same as the boiler power supply, replace
the control board
If wires are damaged, replace them
If the wiring is intact, replace the gas valve
or the control board
a) If the error appears during operation,
replace the control board
b) If the error appears when the boiler is
starting up (using main switch), check that
the limit thermostat (and wiring) is integral
Remove the cause of the Blocking error
If there is no voltage, replace the control
board
If no PWM signal is present, replace
control board
Replace the fan
Control board replacement
Control board replacement
Control board replacement
Control board replacement
Control board replacement
Change the pump or restart it
Open the valves on hydraulic circuit
Replace the safety thermostat
Control board replacement
Control board replacement
Control board replacement
Replace the gas valve
47