Appendix C-PDU Daisy-Chain Function
Does the Host ATS PDU record the Status Records of the Guest ATS PDUs
and itself?
Yes, the Host ATS PDU records the Status Records for all the ATS PDUs in the
daisy-chain.
Will the Status Records of the Guest ATS PDUs logged in the Host ATS PDU
be cleared if the Guest ATS PDUs are disconnected from the Host ATS PDU?
Yes, once the Guest ATS PDUs are removed, the Status Records logged in the
Host ATS PDU will be cleared. As long as the Host ATS PDU does not connect
to other ATS PDUs, the Status Records of the disconnected ATS PDU can be
displayed when it is re-connected to the Host ATS PDU. If the Host ATS PDU
connects to different ATS PDUs, the Status Records of the removed ATS PDU
will be entirely cleared.
Are the Guest ATS PDUs able to connect to the network when they are
daisy-chained?
Yes, even when the ATS PDUs are daisy-chained, the Guest ATS PDUs are
able to connect to the network directly. Note that a Guest ATS PDU will
require having its own Ethernet cable connected to the network.
What will happen if a 5th ATS PDU is added to a daisy-chain?
The maximum number of ATS PDUs that can be connected in one daisy-
chain is 4. The daisy-chain functionality will not work until the fifth ATS PDU
is removed.
What is the maximum recommended length of the Ethernet cable to
daisy-chain the ATS PDUs?
50 ft (15 m)
Troubleshooting
Problem
The
s are
ATS PDU
connected but the
daisy-chain function
is not working.
I cannot set the
EnergyWise
configuration on a
Guest
ATS PDU
I cannot set the WoL
for Guest
ATS PDU
Appendix D-RJ45/ DB9 Serial Port
Connection Cable Pinout:
Pinout of RJ45 plug and DB9 socket provided in package are shown below.
RJ45 Plug
(Male)
Possible Cause
- The firmware
version does not
support daisy-
chain.
- The
dierent firmware
versions.
Only the Host
ATS PDU
EnergyWise.
.
Only the Host
s.
supports WoL.
PDU
DB9 Socket
(Female)
s have
ATS PDU
supports
ATS
35
Solution
Check the firmware
version of each
and upgrade it
PDU
to v1.2.2 or above.
N/A
N/A
Pin1
Pin2
GND
Pin3
Pin4
Pin5
Pin6
Pin7
Pin8
ATS
N/A
N/A
N/A
N/A
RX
N/A
TX