Firmware Upgrade

By upgrading the Firmware, you can obtain new features and updates/
improvements to existing functionality. To ensure the firmware is kept up to
date, please regularly visit our website to see if there is any updated firmware
version available .
• Switched Metered by Outlet/ Metered by Outlet/ Switched/ Monitored Series:
There are four methods for upgrading the ATS PDU firmware. Please
follow the instructions below for the method that is appropriate for
your application. There are two files to update in order to upgrade the
firmware version:
* cpsmpdumafw_XXX.bin
* cpsmpdumadata_XXX.bin
• Metered Series:
You can use a USB Flash Drive to upgrade the ATS PDU firmware. Please
follow the instructions below for using a USB Flash Drive. There is one file
to update in order to upgrade the firmware version:
* cpsmpdumcfw_XXX.bin
Note that the XXX is not part of the file name but is where the version
number in the filename is given.
Prior to performing a firmware update, please:
• Download the latest firmware from www.cyberpower.com.
• Extract the downloaded firmware file to your local "C:\" drive.
Note:
1. The FTP service needs to be enabled before attempting to execute a
firmware upgrade.
2. Please do not turn the ATS PDU off when performing the firmware
upgrade. ATS PDU outlets will remain powered on while the firmware
update takes place. Only the ATS PDU LCD screen will reboot.
3. The ATS PDU LCD screen will reboot during the firmware update process.
This DOES NOT cause the ATS PDU outlets to reboot.
Option 1: Single Device Upgrade
Use the following steps to upgrade the firmware.
1. Open a command prompt window and navigate to "C:\".
2. Login to the ATS PDU with FTP command, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126 is the
current IP of the ATS PDU and 21 is the default ftp port for the
ATS PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
3. Upload the cpsm cpsmpdumafw_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumafw_XXX.bin
4. Upgrade complete, type
- ftp > quit
5. The system will reboot after you type "quit". This reboot will take approx. 30
seconds.
6. Login to the ATS PDU via FTP again, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126 is the
current IP of the ATS PDU and 21 is the default ftp port for the
ATS PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
7. Upload cpsmpdumadata_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumadata_XXX.bin
22