When Using A Solid Pack Chimney; When Using An Air Cooled Chimney - Napoleon HIGH COUNTRY NZ6000-1 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

5.1

when using a solid pack chimney

Cement board and steel studs
on enclosure ceiling not
required above 10' (3.1m)
Face must have a
minimum 8' (2.4m)
height of cement
board depending
upon ceiling height
Combustible
facing and wood
framing may start
at 8' (2.4m) above
the base of the unit
Cement board from
the side of the unit
to combustibles
NOTE: For more information on ventilation openings (Fig. 1 and Fig. 2 above), see section 3.1.1 "Ventilation
Openings" of this manual.
5.2

when using an air cooled chimney

Cement board
FIG. 1
FIG. 2
Cement board
Face must have a
minimum 7' (2.1m)
height of cement board
Combustible
facing and wood
framing may start
at 7' (2.1m) above
the base of the unit
Cement board from
the side of the unit
to combustibles
Metal Studs
MINIMUM 7' (2.1m) TO BASE OF THE FIREPLACE
Enclosure ceiling
height from 7 ' (2.1m)
to 10 ' (3.1m)
Metal Studs
21
ENCLOSURE CEILING
FLOOR JOISTS
METAL STUDS
CEMENT BOARD
The appliance face and
enclosure ceiling must
be framed using 2x4
metal studs.
The minimum enclosure
ceiling height is 7 feet
(2.1m).
Non-combustible
materials (cement board
and metal studs) must
be used.
W415-1501 / C / 10.11.17