OPERATING PROCEDURE
3. Removing the electrical parts box
(1) Remove the service panel. (Refer to procedure 1)
(2) Remove the top panel. (Refer to procedure 1)
(3) Disconnect the indoor/outdoor connecting wire and
power supply wire from terminal block.
(4) Disconnect the connectors of CNF1, CNF2, 63HS, LEV-
A, LEV-B and LEV-C on the controller circuit board.
<Symbols on the board>
• CNF1, CNF2: Fan motor
• 63HS: Pressure Sensor
• LEV-A, LEV-B, LEV-C: LEV-A, LEV-B, LEV-C
Remove the lead wires of LEV and 63HS from clamp.
Disconnect the pipe-side connections of the following parts.
• Thermistor <Liquid>(TH3)
• Thermistor <Discharge>(TH4)
• Thermistor <2-Phase pipe>(TH6)
• Thermistor <Ambient>(TH7)
• Thermistor <Suction> (TH32)
• Thermistor <Comp. surface> (TH33)
• Thermistor <Plate HEX liquid> (TH34)
• High pressure switch (63H)
• 4-way valve coil (21S4)
(5) Disengage the terminal cover from the hook to remove it.
(6) Remove the fixing screws of the 4-way valve to discon-
nect the compressor lead wire.
(7) Remove the sensor holder from the rear guard on back
of the unit.
(8) Remove 2 electrical parts box fixing screws (4 × 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 5 (PUZ-HWM140V)
Controller circuit board
Terminal
block (TB1)
Clamp
Terminal
block (TB2)
OCH748
Photo 4 (PUZ-HWM140Y)
Noise filter circuit
board (N.F.)
Terminal
block (TB1)
Photo 6
Hook (right)
Hooks (left)
Electrical parts
Photo 7
box fixing screws
Terminal
cover
69
PHOTOS/FIGURES
Controller circuit
board (C.B.)
Terminal
block (TB2)
Electrical
parts box
Electrical parts
box fixing
screws
Clamp