Outdoor power circuit board
PUZ-HWM140YHA(-BS)
Diode module
TAB connector
on X52CA
Connect to the
RS resistor
TB-L1, TB-L2,
TB-L3
Connect to the
outdoor converter
circuit board
(L1-OU, L2-OU, L3-OU)
400 VAC
CN4
Connect to the
outdoor controller
circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1–5: Power circuit board
signal to the controller board (0–5 VDC)
2–5: Zero cross signal (0–5 VDC)
3–4: Not used
6–5: 15 VDC
7–5: 15 VDC
[ 5: −
1, 2, 6, 7: + ]
OCH748
Brief Check of POWER MODULE
If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check of POWER MODULE
1.Check of DIODE circuit
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2.Check of INVERTER circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note: The marks, L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
TB-N
Connect to the CK capacitor
P1
L1
L2
CN5
Detection of primary
current (Connect to
the outdoor noise filter
circuit board (CNCT))
Transmitting
shown in the diagram are not actually printed on the board.
N2
L3
N1
CN7
Connect to the
outdoor converter
circuit board (CN7)
CN6
Thermistor
<Heat sink> (TH8)
43
TB-U, TB-V, TB-W
Connect to the compressor (MC)
Voltage among phases:
10–400 VAC
W
V
U
P2
DIP-IPM