SW2 setting
The outdoor 2-phase pipe tempera-
ture (TH6) when the fourth-to-last error
ON
occurred
−39 to 88
1
2 3 4 5 6
The ambient temperature (TH7) when
ON
the fourth-to-last error occurred
−39 to 88
1
2 3 4 5 6
The heat sink temperature (TH8) when
the fourth-to-last error occurred
ON
-40 to 200
1
2 3 4 5 6
The suction pipe temperature (TH32)
when the fourth-to-last error occurred
ON
−39 to 88
1
2 3 4 5 6
The Comp. surface temperature (TH33)
when the fourth-to-last error occurred
ON
−20 to 217
1
2 3 4 5 6
The LEV-A opening pulse when the
fourth-to-last error occurred
ON
0 to 500
1
2 3 4 5 6
The LEV-B opening pulse when the
ON
fourth-to-last error occurred
0 to 500
1
2 3 4 5 6
The LEV-C opening pulse when the
ON
fourth-to-last error occurred
0 to 500
1
2 3 4 5 6
The LEV-A opening pulse when the last
ON
error occurred
0 to 500
1
2 3 4 5 6
OCH748
Display detail
59
The black square (
Explanation for display
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−40 to 200
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−20 to 217
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
) indicates a switch position.
Unit
°C
°C
°C
°C
°C
Pulse
Pulse
Pulse
Pulse