Refrigerant System Diagram - Mitsubishi Electric PUZ-HWM140VHA Service Manual

Air to water heat pump, outdoor unit, salt proof
Table of Contents

Advertisement

8

REFRIGERANT SYSTEM DIAGRAM

PUZ-HWM140VHA(-BS)
Water OUT
PRV
Plate HEX
Water IN
TH34
Symbol
COMP
Compressor
H/P SW
High pressure switch (63H)
Plate HEX
Plate Heat Exchanger
REV/V
Reversing (4-way) valve (21S4)
STOP VALVE Stop valve
CHECK/V
Check valve
P-Sensor
Pressure sensor (63HS)
P/B
Power board
LEV-A
Linear expansion valve -A
LEV-B
Linear expansion valve -B
LEV-C
Linear expansion valve -C
TH32
Suction temperature thermistor
TH3
Liquid temperature thermistor
TH4
Discharge temperature thermistor
TH6
2-Phase pipe thermistor
TH34
Plate HEX liquid temperature thermistor Heating: Sub cool liquid temperature Cooling: Evaporating temperature
TH7
Ambient temperature thermistor
TH8
Heatsink temperature thermistor
TH33
Comp. surface temperature thermistor For compressor protection
Power
Power Receiver
Receiver
HIC
Heat interchange circuit
OCH748
PUZ-HWM140YHA(-BS)
P-Sensor
STOP VALVE
CHECK/V
Power
Receiver
Strainer
(#100)
LEV-B
Strainer(#100)
Part name
DC inverter scroll compressor (Mitsubishi Electric Corporation)
For protection (OFF: 4.15MPa)
MWA2-34HM(Mitsubishi Electric Corporation)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
For refrigerant charge
High pressure / Low pressure
For calculation of the saturation temperature from refrigerant pressure
Inverter power board
Heating: Secondary LEV
Heating: Primary LEV
For HIC (heating only)
For LEV control
Heating: Evaporating temperature
For LEV control and for compressor protection
Heating: Evaporating temperature Cooling: Condensing temperature
For fan control and for compressor frequency control
For power board protection
For accumulation of refrigerant
For high heating capacity
REV/V
CHECK/V
H/P SW
Strainer
(#100)
TH32
TH33
Strainer
INJ Port
(#100)
COMP
LEV-C
18
TH6
TH7
Distributor
TH4
Strainer(#100)
TH8
P/B
HIC
Refrigerant flow in cooling
Refrigerant flow in heating
Detail
Cooling: Primary LEV
Cooling: Secondary LEV
Cooling: Sub cool liquid temperature
TH3
LEV-A

Hide quick links: