Bb Speed Search Method; Auto Restart Times After Fault - Delta Electronics AC Drive VFD-F Series User Manual

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
08 - 08

BB Speed Search Method

Settings
This parameter determines BB speed search method when multi-function input terminal
04-00 to 04-07 is set to BB External interrupt (11 or 12) and activates.
BB speed search method is the same with restart speed search after momentary loss
power.
08 - 09

Auto Restart Times After Fault

Settings
This parameter determines the times of auto restart after fault.
When AC drive occurs fault (OV, OC or OCC) and fault disappeared automatically, this
parameter allows AC drive reset and runs with the parameter that is set before fault
occurred.
If fault occurred times exceed 08-09 setting, AC drive will reject to restart and need to reset
by users to keep on running.
Master frequency command
08-07
Output voltage
V/F curve setting
00: Trace from top downward
01: Trace from bottom upward
00 ~10
Output frequency
Output voltage
output current
Synchronization attained
Time
Actual V/F output
Output frequency
5-42
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory Setting: 00
Factory Setting: 00