In noisy environments, it would be advantageous to verify the terminal status several times
before executing a new command, nearly eliminating false signals.
Example: If Pr.04-08 is set to 4, the AC drive will confirm the terminal status (4+1 = 5) 5
times before a change is made. This correlates to an 8~10msec time response from input
command to execution.
It is not recommended to set this parameter to 00, since interference may cause improper
operation of the AC drive.
04 - 09

AVI Minimum Voltage

04 - 10

AVI Maximum Voltage

Settings
04 - 11
AVI Minimum Frequency (percentage of Pr.1-00)
04 - 12
AVI Maximum Frequency (percentage of Pr.1-00)
Settings
04 - 13
ACI1 Minimum Current
04 - 14
ACI1 Maximum Current
Settings
04 - 15
ACI1 Minimum Frequency (percentage of Pr.1-00)
04 - 16
ACI1 Maximum Frequency (percentage of Pr.1-00)
Settings
04 - 17
ACI2 Minimum Current
04 - 18
ACI2 Maximum Current
Settings
04 - 19
ACI2 Minimum frequency (percentage of Pr.1-00)
04 - 20
ACI2 Maximum frequency (percentage of Pr.1-00)
Settings
The above parameters are used to set the analog input reference values. The min and max
frequencies are based on Pr.01-00 (during open-loop control) or the PID reference value
Pr.10-01 (during PID close-loop control).
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
0.0 ~ 10.0V
0.00~100.00%
0.0 ~ 20.0mA
0.0~100.0%
0.0 ~ 20.0mA
0.00~100.00%
5-21
VFD-F Series
Factory Setting: 0.0
Factory Setting: 10.0
Unit: 0.1
Factory Setting: 0.00
Factory Setting: 100.00
Unit: 0.01
Factory Setting: 4.0
Factory Setting: 20.0
Unit: 0.1
Factory Setting: 0.00
Factory Setting: 100.00
Unit: 0.01
Factory Setting: 4.0
Factory Setting: 20.0
Unit: 0.1
Factory Setting: 0.00
Factory Setting: 100.00
Unit: 0.01