Mid-point Voltage

Settings
This parameter sets the Mid-point Voltage of the V/f curve.
This parameter must meet the following argument. Pr.1-02 >= Pr.1-04 >= Pr.1-06.
01 - 05

Minimum Output Frequency

Settings
This parameter sets the Minimum Output Frequency of the AC drive. This parameter must
be lower than or equal to the Mid-point frequency
01 - 06

Minimum Output Voltage

Settings
This parameter sets the Minimum Output Voltage of the AC Drive. The parameter must be
lower than or equal to the Mid-point Voltage.
01 - 07

Upper Bound Frequency

Settings
This parameter will limit the maximum output frequency of AC drive. If slip compensation
(Pr.07-02~07-05) or feedback control (Pr.10-00~10-09) are enabled, the output frequency
of AC drive may exceed the Master Frequency Command, but it will continue to be limited
by this parameter setting.
01 - 08
Lower Bound Frequency
Settings
This parameter will limit the minimum output frequency. Any Master Frequency Command
below Pr.1-08, will result in an output equal to Pr.1-08.
Upon a start command, the drive will accelerate from Pr.1-05 Minimum Output Frequency
to the Master Frequency Command point.
The Lower Bound Frequency setting must be smaller than the Dwell Frequency
(Pr.11-08>=01-08). If lower bound frequency setting is greater than the Dwell Frequency,
the AC drive will equalize the two settings to the Lower Bound point.
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
230V series: 0.1 ~ 255.0V
460V series: 0.2 ~ 510.0V
0.10~20.00 Hz
230V series: 0.1 ~ 50.0V
460V series: 0.2 ~100.0V
0.00~120.00 Hz
0.00~120.00 Hz
5-5
VFD-F Series
Factory Setting: 5.5/11.0
Factory Setting: 1.50
Factory Setting: 5.5/11.0
Factory Setting: 60.00
Factory Setting: 0.00