B.4 Non-fuse Circuit Breaker Chart
The fuse should comply with UL248 and the breaker should comply with UL489.
The current rating of the breaker shall be within 2~4 times maximum input current rating.
Model
VFD007F23A
VFD007F43A/H
VFD015F23A
VFD015F43A/H
VFD022F23A
VFD022F43A/H
VFD037F23A
VFD037F43A/H
VFD055F23A
VFD055F43B/H
VFD075F23A
VFD075F43B/H
VFD110F23A
VFD110F43A/H
VFD150F23A
VFD150F43A/H
VFD185F23A
VFD185F43A/H
VFD220F23A
VFD220F43A/H
VFD300F23A
VFD300F43A/H
VFD370F23A
VFD370F43A/H
VFD450F43A/H
VFD550F43A/H
VFD750F43A/H
VFD900F43C/H
VFD1100F43C/H
VFD1320F43A/H
VFD1600F43A/H
VFD1850F43A/H
VFD2200F43A/H
3-phase
Recommended non-fuse breaker (A)
10
15
10
30
15
40
20
50
30
60
40
100
50
125
60
150
75
175
100
225
125
250
150
175
250
300
300
400
500
600
600
800