Temperature Mode And Sub-Mode Directory - Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Operation And Service Manual

Air-cooled chillers with comfortlink controls
Hide thumbs Also See for AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060:
Table of Contents

Advertisement

KEYPAD
SUB-MODE
ENTRY
UNIT
ENTER
CIR.A
ENTER
CIR.B
ENTER
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
SUB-MODE
ENTRY
PRC.A
ENTER
PRC.B
ENTER
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
SUB-MODE
ENTRY
COOL
ENTER
HEAD
ENTER
FRZ
ENTER
Table 5 — Temperature Mode and Sub-Mode Directory
ITEM
DISPLAY
XXX.X F
CEWT
XXX.X F
CLWT
XXX.X F
OAT
XXX.X F
SPT
XXX.X F
DLWT
XXX.X F
SCT.A
XXX.X F
SST.A
XXX.X F
RGT.A
XXX.X F
D.GAS
SH.A
XXX.X ^F
XXX.X F
SCT.B
XXX.X F
SST.B
XXX.X F
RGT.B
SH.B
XXX.X ^F
Table 6 — Pressure Mode and Sub-Mode Directory
ITEM
DISPLAY
DP.A
XXX.X PSIG
SP.A
XXX.X PSIG
DP.B
XXX.X PSIG
SP.B
XXX.X PSIG
Table 7 — Set Points Mode and Sub-Mode Directory
ITEM
DISPLAY
XXX.X F
CSP.1
XXX.X F
CSP.2
XXX.X F
CSP.3
XXX.X F
H.DP
XXX.X F
F.ON
XXX.X F
F.OFF
XXX.X F
B.OFF
XXX.X F
F.DLT
XXX.X F
BR.FZ
ITEM
EXPANSION
ENT AND LEAVE UNIT TEMPS
COOLER ENTERING FLUID
COOLER LEAVING FLUID
OUTSIDE AIR TEMPERATURE
SPACE TEMPERATURE
LEAD/LAG LEAVING FLUID
TEMPERATURES CIRCUIT A
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPR RETURN GAS TEMP
DISCHARGE GAS TEMP
SUCTION SUPERHEAT TEMP
TEMPERATURES CIRCUIT B
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPR RETURN GAS TEMP
SUCTION SUPERHEAT TEMP
ITEM
EXPANSION
PRESSURES CIRCUIT A
DISCHARGE PRESSURE
SUCTION PRESSURE
PRESSURES CIRCUIT B
DISCHARGE PRESSURE
SUCTION PRESSURE
ITEM
EXPANSION
COOLING SETPOINTS
COOLING SETPOINT 1
COOLING SETPOINT 2
ICE SETPOINT
HEAD PRESSURE SETPOINTS
HEAD SETPOINT
FAN ON SETPOINT
FAN OFF SETPOINT
BASE FAN OFF DELTA TEMP
FAN STAGE DELTA
BRINE FREEZE SETPOINT
BRINE FREEZE POINT
9
COMMENT
See Note
See Note
See Note
See Note
See Note
COMMENT
See Note
See Note
See Note
COMMENT
Default: 44 F
Default: 44 F
Default: 32 F
Default: 95 F
Default: 95 F
Default: 72 F
Default: 23 F
Default: 15 F
Default: 34 F