Fault Codes - Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Operation And Service Manual

Air-cooled chillers with comfortlink controls
Hide thumbs Also See for AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060:
Table of Contents

Advertisement

FAULT CODE
AF
CF
cF
CL
GF
HF
JF
LF
OF
PF
SF
F1
F2-F9, Fo
Drive display = 60.0 even though it
is cold outside and it should be run-
ning slower
Drive display = '---' even though
drive should be running
Drive display = 8.0 even though fan
should be running faster
VFD flashes 57 and LCS
LEGEND
EPM
— Electronic Programming Module
LCS
— Lost Control Signal
OEM
— Outside Equipment Manufacturer
VFD
— Variable Frequency Drive
Table 38 — Fault Codes
DESCRIPTION
High Temperature Fault: Ambient temperature is too high;
Cooling fan has failed (if equipped).
Control Fault: A blank EPM, or an EPM with corrupted data
has been installed.
Incompatibility Fault: An EPM with an incompatible parame-
ter version has been installed.
CURRENT LIMIT: The output current has exceeded the
CURRENT LIMIT setting (Parameter 25) and the drive is
reducing the output frequency to reduce the output current.
If the drive remains in CURRENT LIMIT too long, it can trip
into a CURRENT OVERLOAD fault (PF).
Data Fault: User data and OEM defaults in the EPM are
corrupted.
High DC Bus Voltage Fault: Line voltage is too high; Decel-
eration rate is too fast; Overhauling load.
Serial Fault: The watchdog timer has timed out, indicating
that the serial link has been lost.
Low DC Bus Voltage Fault: Line voltage is too low.
Output Transistor Fault: Phase to phase or phase to ground
short circuit on the output; Failed output transistor; Boost
settings are too high; Acceleration rate is too fast.
Current Overload Fault: VFD is undersized for the applica-
tion; Mechanical problem with the driven equipment.
Single-phase Fault: Single-phase input power has been
applied to a three-phase drive.
EPM Fault: The EPM is missing or damaged.
Internal Faults: The control board has sensed a problem
Feedback signal is above set point
Start jumper is missing
Feedback signal is below set point and fan is at minimum
speed
Feedback or speed signal lost. Drive will operate at 57 Hz
until reset or loss of start command. Resetting requires
cycling start command (or power).
Check cooling fan operation
Perform a factory reset using Parameter 48 —
PROGRAM SELECTION.
Either remove the EPM or perform a factory
reset (Parameter 48) to change the parameter
version of the EPM to match the parameter
version of the drive.
Check for loose electrical connections.
Check for faulty condenser fan motor.
Check Parameter P25 from Table 39 is set
correctly.
Restore factory defaults P48, see section
above. If that does not work, replace EPM.
Check line voltage — set P01 appropriately
Check serial connection (computer)
Check settings for PXX.
Check settings in communication software to
match PXX.
Check line voltage — set P01 appropriately
Reduce boost or increase acceleration values.
If unsuccessful, replace drive.
Check line voltage — set P01 appropriately
Check for dirty coils
Check for motor bearing failure
Check input power phasing
Consult factory
Check for proper set point
Check liquid line pressure
Replace start jumper. See section above
Check for proper set point
Check liquid line pressure
In stand alone mode: Check transducer wiring
and feedback voltage. Feedback voltage dis-
played on P-69. Pin 6 should be 5 v output.
Pin 5 (feedback) should be somewhere
between 0 and 5 v.
61
SOLUTION