ALARM/
ALARM
ALERT
OR
DESCRIPTION
CODE
ALERT
Circuit A, Compressor 1
T051
Alert
Failure
Circuit A, Compressor 1
A051
Alarm
Failure
Circuit A, Compressor 2
T052
Alert
Failure
Circuit A, Compressor 2
A052
Alarm
Failure
Circuit B, Compressor 1
T055
Alert
Failure
Circuit B, Compressor 1
A055
Alarm
Failure
Circuit B, Compressor 2
T056
Alert
Failure
Circuit B, Compressor 2
A056
Alarm
Failure
Cooler Leaving Fluid
A060
Alarm
Thermistor Failure
Cooler Entering Fluid
A061
Alarm
Thermistor Failure
T068
None
Circuit A Return Gas Thermistor Failure
T069
None
Circuit B Return Gas Thermistor Failure
Outside Air Thermistor
T073
Alert
Failure
Space Temperature/Dual Chiller
T074
Alert
Thermistor Failure
Circuit A Saturated
Suction Temperature
T077
Alert
exceeds Cooler Leaving
Fluid Temperature
Circuit B Saturated
Suction Temperature
T078
Alert
exceeds Cooler Leaving
Fluid Temperature
Lead/Lag LWT
T079
Alert
Thermistor Failure
Circuit A Discharge
T090
Alert
Pressure Transducer Failure
Circuit B Discharge
T091
Alert
Pressure Transducer Failure
Circuit A Suction
T092
Alert
Pressure Transducer Failure
Circuit B Suction
T093
Alert
Pressure Transducer
Failure
Discharge Gas
T094
Alert
Thermistor Failure
Table 42 — Alarm and Alert Codes
WHY WAS THIS
ALARM
GENERATED?
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Compressor feedback signal
does not match relay state
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F (–40 to 118 C)
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F –40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor.
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor.
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Outside of range (0 to
667 psig)
Outside of range (0 to
667 psig)
Outside of range (0 to 420
psig)
Outside of range (0 to
420 psig)
Discharge thermistor (DTT) is
either open or shorted
67
ACTION TAKEN
RESET
BY CONTROL
METHOD
Compressor A1 shut
Manual
down.
Unit shut down
Manual
Compressor A2 shut
Manual
down.
Unit shut down
Manual
Compressor B1 shut
Manual
down.
Unit shut down
Manual
Compressor B2 shut
Manual
down.
Unit shut down
Manual
Chiller shut down
Automatic
immediately
Chiller shut down
Automatic Thermistor failure, damaged
immediately
Circuit A shut down
Automatic
Circuit B shut down
Automatic
Temperature reset
disabled. Chiller runs
under normal control/set
Automatic
points. When capacity
reaches 0, cooler/pump
heaters are energized.
Temperature reset
disabled. Chiller runs
Automatic
under normal control/set
points.
Circuit A shutdown after
Automatic
pumpdown complete.
Circuit B shutdown after
Automatic
pumpdown complete
Chiller runs as a stand
Automatic
alone machine
Circuit A shut down
Automatic
Circuit B shut down
Automatic
Circuit A shut down
Automatic
Circuit B shut down
Automatic
Digital compressor shut
Automatic
down.
PROBABLE
CAUSE
High-pressure switch open,
faulty CSB, loss of condenser
air, filter drier plugged, non-
condensables, operation
beyond capability.
Welded compressor contac-
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
air, filter drier plugged, non-
condensables, operation
beyond capability.
Welded compressor contac-
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
air, filter drier plugged, non-
condensables, operation
beyond capability.
Welded compressor contac-
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
air, filter drier plugged, non-
condensables, operation
beyond capability.
Welded compressor contac-
tor, CSB wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Faulty expansion valve or
suction pressure transducer
or leaving fluid
thermistor.
Faulty expansion valve or
suction pressure transducer
or leaving fluid
thermistor.
Dual LWT thermistor failure,
damaged cable/wire or
wiring error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Transducer failure, poor
connection to MBB, or wiring
damage/error.
Thermistor failure, damaged
cable/wire or wiring error.