Table 3-2 Alarm Codes - Carrier GR-45 Operation And Service

Bus air conditioning unit
Table of Contents

Advertisement

ALARM
TITLE
NO.
A11
Coil Freeze
A12
High Voltage
A13
Low Voltage
A14
Return Air Probe Failure
A15
Suction Pressure
Transducer Failure
A16
Discharge Pressure
Transducer Failure
A17
Low Pressure Shutdown
A21
High Discharge Pressure

Table 3-2 Alarm Codes

CAUSE
Coil temperature is
Check causes of coil
less than 32F and the
freezing. (Refer to
compressor is operat-
section 3.3.6)
ing.
The battery voltage is
Check, repair or re-
greater than 32 volts.
place alternator.
The battery voltage is
Check, repair or re-
less than 17 volts.
place wiring or alter-
nator.
Return air temperature
Ensure all connectors
sensor failure or wir-
are plugged in. Check
ing defective.
sensor resistance or
wiring. Refer to para-
graph 4.21. Replace
sensor or repair wir-
ing.
Suction pressure
Ensure all connectors
transducer failure or
are plugged in. Check
wiring defective.
sensor voltage or wir-
ing. Replace sensor or
repair wiring.
Discharge pressure
Ensure all connectors
transducer failure or
are plugged in. Check
wiring defective.
sensor voltage or wir-
ing. Replace sensor or
repair wiring.
Low suction pressure
Check cause of low
switch open or wiring
suction pressure. (Re-
defective.
fer to section 3.5.3)
High discharge pres-
Check discharge pres-
sure switch open or
sure transducer read-
wiring defective.
ing, wiring or cause of
high discharge pres-
sure. (Refer to section
3.3.3)
3-2
REMEDY
CONTROLLER
RESPONSE
An alarm will be gener-
ated and the system will
shutdown. The evapora-
tor fans will remain run-
ning while the compres-
sor is off.
The system is shut down
until the voltage returns
to normal levels.
The system is shut down
until the voltage returns
to normal levels.
All outputs except the
evaporator fans will be
de-energized.
Both unloaders are ener-
gized.
One unloader is ener-
gized.
The clutch is de-ener-
gized for the minimum
off time. The evaporator
fans will remain running
during this period. After
the compressor cycles
off three times in 30
minutes all outputs will
be de-energized and the
system is locked out un-
til the power is cycled or
the alarm is reset.
The clutch is de-ener-
gized for the minimum
off time. The condenser
and evaporator fans will
remain running during
this period. After the
compressor cycles off
three times in 30 min-
utes all outputs will be
de-energized and the
system is locked out un-
til the power is cycled or
the alarm is reset.
T--295